G-Force
INSTRUCTION FOR INSTALLATION, SAFE OPERATION, AND MAINTENANCE
SAMPLE CONFIGURATIONS
BOOSTER and BOOSTER OSC
SECONDARY LDH INLET
FOR MONITORS
DANGER
Understand manual before use. Operation of this device without understanding the manual and
receiving proper training is a misuse of this equipment. Obtain safety information at tft.com/
serial-number.
This equipment is intended for use by trained and qualified emergency services personnel for
firefighting. All personnel using this equipment shall have completed a course of education
approved by the Authority Having Jurisdiction (AHJ).
This instruction manual is intended to familiarize firefighters and maintenance personnel with the
operation, servicing, and safety procedures associated with this product. This manual should be
kept available to all operating and maintenance personnel.
Model ZCF1T3
integrated with
TFT Hydrant Under Monitor
and TFT Monsoon Monitor
Model ZCH1T1-OSC
for attachment to Hydrants,
Valves and Monitors with
4" ANSI 150 connections
Model ZCH1TQ
integrated with
TFT Industrial Valve Under Monitor and
4.5" NH Quick Connect for TFT monitor
HYDROSTATIC PROOF TEST:
800 psi (55 bar)*
*Do not exceed the rated operating pressure of 200 psi (14 bar).
Per FM 1421 the hydrostatic proof test is performed on a sample
valve to ensure it does not visibly rupture, crack or permanently
distort at 4 times the rated operating pressure. The purpose of the
proof test is to be confident the valve design may be safely
operated at the rated operating pressure.
RATED OPERATING PRESSURE:
200 PSI (14 BAR)
SAFE OPERATING RANGE FOR MONITOR OUTLET:
Booster and Booster OSC: 2000 gpm @ 200 psi
(8000 l/min @ 14 bar).
Booster only (not OSC): 2500 gpm @ 130 psi
(9500 l/min @ 9 bar).