background image

©Copyright Task Force Tips, Inc. 2010 

LIA-420 July 12, 2010 Rev00

7

5.5 FLOW INCREASE FROM BOOSTING

FLOW/GPM

WITHOUT BOOST

GALLONS OF WATER PER MINUTE FLOWING THROUGH 

VARIOUS LENGTHS AND SIZES OF HOSE WITH AND 

WITHOUT PRESSURE ADDED BY BOOST PUMPER

4" HOSE

5" HOSE

500 ft.

1000 ft.

1500 ft.

500 ft.

1000 ft.

1500 ft.

MODE 1

NOMINAL HYDRANT 

PRESSURE

60

780

550

450

1240

870

710

MODE 2 

BOOST

PRESSURE ADDED 

BY BOOST PUMPER 

(TOTAL PRESSURE)

90

 (150)

1240

870

710

1960

1380

1120

140

 (200)

1430

1010

820

2240

1580

1290

NOTE: (1) Flow rates calculated assuming that 10 psi residual is remaining at the inlet to the attack pumper.

5.6 VALVE PRESSURE LOSS

OASIS HYDRANT ASSIST VALVE PRESSURE LOSS

0

10

20

30

40

50

60

0

500

1000

1500

2000

FLOW (GPM)

P

R

ESSU

R

E L

O

SS (

P

SI

)

SIDE PORT 

FLOW

57 PSI at 2000 GPM

STRAIGHT THROUGH

FLOW

43 PSI at 2000 GPM

6.0 MAINTENANCE

This valve should be disconnected, cleaned and visually inspected inside and out at least quarterly for proper function per NFPA 
1962 section 8.2, or as water quality and use may require.  Moving parts such as handles, valve ball and couplings should be 
checked for smooth and free operation.  Seals shall be greased as needed with a silicone-based grease such as Dow Corning 112.  
Any scrapes that expose bare aluminum should be cleaned and touched up with enamel paint such as Rust-Oleum.  

In particular assure that:

There is no damage such as cracks or dents

• 

There is no corrosion

• 

The waterway is clear of obstructions

• 

Replace any missing or damaged parts before returning to service.  Any repaired device must be tested before being placed in 
service.

CAUTION

Any alterations to the device and its markings could diminish safety and constitute a misuse 
this product

Summary of Contents for OASIS HYDRANT ASSIST VALVE

Page 1: ...ualified to operate the Oasis Hydrant Assist Valve Please call 800 348 2686 with any questions WARNING This instruction manual is intended to familiarize firefighters and maintenance personnel with th...

Page 2: ...4 PARALLEL DRIVE GEARBOX 8 0 WARRANTY 1 0 MEANING OF SAFETY SIGNAL WORDS A safety related message is identified by a safety alert symbol and a signal word to indicate the level of risk involved with...

Page 3: ...lve provides corrosion protection Maximum operating pressure is 250 psi 17 bar Meets 900 psi 62 bar hydrostatic strength test The aluminum casting is hardcoat anodized inside and out and TFT powder co...

Page 4: ...he shorter offset is available to avoid interference with other equipment To change the offset remove the two 1 4 20 x 1 2 button head cap screws from crank Place crank in desired position and replace...

Page 5: ...GE MODE 2 BOOST Hydrant Pressure to Assist Pumper Boosted Flow to Attack Engine ATTACK ASSIST A B C1 C2 R E L A Y P U M P E R HYDRANT ASSIST 800 348 2686 Valparaiso IN 46383 9327 TASK FORCE TIPS Read...

Page 6: ...g off TO RELAY PUMP INLET Clapper indictor showing clapper shutting off FROM PUMP RELAY port and allowing water to flow directly from the HYDRANT port to the TO FIRE port When water is supplied from a...

Page 7: ...PORT FLOW 57 PSI at 2000 GPM STRAIGHT THROUGH FLOW 43 PSI at 2000 GPM 6 0 MAINTENANCE This valve should be disconnected cleaned and visually inspected inside and out at least quarterly for proper func...

Page 8: ...128 5 RELAY VALVE BODY 1 A2010 6 LABEL CLAPPER POSITION INDICATOR 1 A2012 7 1 8 NPT PLUG 2 VFSP1M SS 8 O RING 243 2 VO 243 9 MOUNTING FOOT 4 A2037 10 O RING 115 1 VO 115 11 LOWER TRUNNION 1 AY353 12...

Page 9: ...55N A4660N A4665N A4670N 87 PORT PLUG A1299 A1299 A1299 A1299 88 CUP SEAL A1597 A1596 A1596 A1596 89 PLASTIC STRIP A1292 A1291 A1291 A1291 90 MATE A2015 A2016 A2016 A2016 FEMALE HOSE THREADS ROCKER LU...

Page 10: ...299 A1299 A1299 97 COUPLING A4555NP A4568NR A4573NT 99 PLASTIC STRIP A1291 A1293 A1293 100 MATE A2017 A2019 A2019 FREE SPINNING COUPLINGS DO NOT USE CUP SEALS 7 3 CLAPPER 27 32 31 30 29 28 27 26 23 22...

Page 11: ...1 A1550 47 O RING 116 1 VO 116 48 SPACER 1 A1556 49 DRIVE SHAFT 1 A1555 50 NYLON BUSHING 1 AY307 51 GEAR BUSHING 1 A1548 52 DOUBLE GEAR 1 A1554 53 TRUNNION BUSHING 1 A1549 54 INNER TRUNNION 1 A1553 55...

Page 12: ...equipment less reasonable depreciation in complete discharge of its obligations under this limited warranty If TFT makes this election claimant shall return the equipment to TFT free and clear of any...