12
The full scale range of the ammeter is dependant on the loading unit. A switch is provided on
the PCU2 to switch the meter between the series and parallel range.
Loading Unit
Output
arrangement
Ammeter
range
Meter full
scale
Resolution
Accuracy
LU5000
LU8000
Series
Low
2500A
1A
0.6% 6d
High
5.00kA
10A
0.6% 6d
Parallel
Low
5000A
1A
0.6% 6d
High
10.00kA
10A
0.6% 6d
LU6000
Series
Low
3000A
1A
0.6% 6d
High
6.00kA
10A
0.6% 6d
Parallel
Low
6000A
1A
0.6% 6d
High
12.00kA
10A
0.6% 6d
If the metering cable is not connected between the PCU2 MK5 control unit and the external
loading unit, the ammeter will not function and the output will not switch on.
1.2.5
Overload trip
The output of the unit is protected by an overload trip that operates at approximately 115% of
full load current.
Loading Unit
Output
arrangement
Metering range
Overload trip
current
LU5000
LU8000
Series
Low
2875A
High
5750A
Parallel
Low
5750A
High
11500A
LU6000
Series
Low
3450A
High
6900A
Parallel
Low
6900A
High
13800A
The unit is also protected by a circuit breaker on the control unit output. This will trip before the
electronic trip on high range (at approximately 10000A for an LU5000/8000 or 12000A for an
LU6000).
Summary of Contents for PCU2 mk5
Page 2: ......
Page 8: ...8 1 1 Front Panel Layout Figure 1 1 PCU2 and loading unit front panels...
Page 20: ......
Page 26: ......
Page 28: ......