background image

 
 

             

TX7100 

 

Intelligent Addressable Optical Smoke Detector 

Installation and Operation Manual  

 
 
 
 
 
 
 

 

 

 

 

 

 

 

 

 

 

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 

 

TANDA UK Technology Copyright ©2015, All right reserved. 

Summary of Contents for TX7100

Page 1: ...TX7100 Intelligent Addressable Optical Smoke Detector Installation and Operation Manual TANDA UK Technology Copyright 2015 All right reserved ...

Page 2: ... marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union For proper recycling return this product to your local supplier upon the purchase of equivalent new equipment or dispose of it at designated collection points For more information please visit the website at www recyclethis info EN54 Part 7 Compliance TX7100 Intelligent Smoke Detector complies with the...

Page 3: ...troduction 4 1 1 Overview 4 1 2 Feature and Benefits 4 1 3 Technical Specification 4 2 Installation 5 2 1 Installation Preparation 5 2 2 Installation and Wiring 5 3 Detector Configuration 6 3 1 Preparation 6 3 2 Write Addressing 6 3 3 Set LED On Off 6 3 4 Read Configuration 7 4 General Maintenance 7 4 1 Cleaning 8 5 Troubleshooting Guide 8 Appendix 1 9 Limitation of Smoke Detectors 9 ...

Page 4: ...e scenarios and smoke patterns for a faster and safer response Once it is confirmed the LED indicates the sensor status and parallel sending communication signal to the control panel The TX7100 detector is compatible to the TX7004 Analogue Intelligent Fire Alarm Control Panel produced by single manufacture T A to avoid addressable communication compatibility problem 1 2 Feature and Benefits EN54 7...

Page 5: ...take place such kitchens or similar areas where steam and condensation are present Where exhaust fumes are present like car parks Where smoke particles will not be produced by fire Plant Rooms unless full discussions regarding the room contents and status subject to a fire have been made between Client and Manufacturer Boiler and Generator Rooms 2 2 Installation and Wiring 1 Mount the T A standard...

Page 6: ...ng cable to 1 and 6 terminals Figure 3 Press Power to switch on the unit 2 Switch on the programmer then press button Write or number 2 to enter Write Address mode Figure 4 3 Input the desire device address value from 1 to 254 and then press Write to save the new address Figure 5 Note If display Success means the entered address is confirmed If display Fail means failure to program the address Fig...

Page 7: ...ol panel to prevent false alarm 3 Do not attempt to adjust or modify the detector it may affect the ability of the detector to respond to a fire condition and will void the manufacturer s warranty 4 Use a damp cloth to clean the detector Do not use cleaning chemicals that may leave residue on the electronic parts and smoke chamber 5 Notify again proper personnel after conducting the maintenance an...

Page 8: ...ash with running water and ensure it is completely dry 4 Position the chamber and screen by aligning three tiny holes over the sensing component Figure 12 5 Align the LED tube and tabs and gently pushing the cover until it locks into place Figure 12 6 Re install and test the detector 5 Troubleshooting Guide What you notice What it means What to do Address not enrolling The wiring is lose The addre...

Page 9: ...leaking gas improper storage of flammable materials like diluents and other safety hazards arson or children playing with fire The alarm of a smoke detector used in high velocity environment will be delayed due to dilution of smoke by frequent and fast airflow What s more the smoke detector has to be frequently maintained for it is exposed to more dust contamination The smoke detector cannot last ...

Reviews: