TD9300 Installation and Configuration Manual
57
© Tait International Limited September 2018
7
Confirming Operation
This section describes the procedures needed to verify and determine
whether the TD9300 is working properly within the GridLink system.
1.
Make sure that the TD9300 is connected to the correct supply volt-
age. See
“DC Connector” on page 21
.
For troubleshooting the supply voltage, refer to
“Troubleshooting”
on page 61
.
2.
Make sure that the TD9300 is connected to an outstation device
(RTU/IED).
3.
Check that the LEDs indicate normal operation, as described in
“LEDs” on page 17
.
If not, then refer to
“Troubleshooting” on page 61
.
4.
With TD9300 firmware version 1.10 or later, the Web UI
Diagnostics menu provides test functions for installation and
commissioning use.
■
Site Select:
Force the TD9300 to a specific DMR control channel to
compare signal strength (RSSI) measurements between sites. Enter the
channel number, select the
Logical channel
(DMR slot), and click
Select
.