10.7 LEVEL_2 Parameter
t
n
e
t
n
o
C
l
o
b
m
y
S
r
e
t
e
m
a
r
a
P
Range
Default
Hide/
MAX
MIN
Display
Main output proportional band
P1
0.0 : ON/OFF control
200.0
0.0
3.0
---
Other values : proportional band setting
value
Main output integral time
I1
0 : disable integral function
3600
0
240
---
Other values : integral time setting value
Main output derivative time
D1
0 : disable derivative function
900
0
60
---
Other values : derivative time setting value
AT.VL
Auto tuning offset value
100.0
-100.0
0.0
---
execute auto tuning in (SV-ATVL) point
Main output control cycle
CYT1
0 : Linear signal
150
0
10
---
1 : SSR drive
2~150 : Relay
Hysteresis for main output
on/off control use(when P1 = 0.0 appear)
heating formula
:
HYS1
PV
≥
(SV + HYS1)
OUT1=OFF
100.0
-100.0
1.0
P1 = 0.0
PV
≤
(SV - HYS1)
OUT1=ON
cooling formula
:
PV
≥
(SV + HYS1)
OUT1=ON
PV
≤
(SV - HYS1)
OUT1=OFF
Sub output proportional band
P2
0.0 : ON/OFF control
200.0
0.0
3.0
OUTY = 1
Other values : proportional band setting
value
Sub output integral time
I2
0 : disable integral function
3600
0
240
OUTY = 1
Other values : integral time setting value
Sub output derivative time
D2
0 : disable derivative function
900
0
60
OUTY = 1
Other values : derivative time setting value
Sub output control cycle
CYT2
0 : Linear signal
150
0
10
OUTY = 1
1 : SSR drive
2~150 : Relay
HYS2
Hysteresis for sub output
100.0
-100.0
1.0
P2 = 0.0
on/off control use(when P2 = 0.0 appear)
GAP1
Control gap (for main output)
1000
-1000
0
OUTY = 1
GAP2
Control gap (for sub output)
1000
-1000
0
OUTY = 1
Function or level lock
LCK
(Please refer to Chapter 10.3 Data Lock
1111
0000
0000
---
Function)
FY/FU operation manual
24