Example(2) Single RAMP+SOAK_B (ALD3=9 + ALD1=19)
Boot completed, the alarm1 is OFF, SV rise 5.00°C rise per minute. when the PV reaches 100 °C, the temperature is kept
for 10 minutes. after 10 minutes alarm is turned ON and the control function keep ON
Parameter setting
Level
Parameter
Set value
Description
1
SV
100.0
Target temperature
4
SET2.1
1
Display AL3
4
SET4.1
1
Display ALD3
3
ALD1
19
AL1 as soak alarm
3
ALD3
9
Enable RAMP function
1
SOAK(AL1)
0.10
10 minute temperature maintain
1
RAMP(AL3)
5.00
5.00°C rise per minute
Temperature
Time up
Alarm=ON
100.0
PV
PV follows SV up 5°C
per minute
ramp start
alarm=ON
PV time chart
25.0
time
5
RAMP
SOAK
15 minutes
10 minutes
seconds
Action
AL1 time chart
ON
time
OFF
Example(3) use only SOAK_A (ALD1=10)
Boot completed, the alarm1 is ON, and the PV is directly controlled at 100 °C. when the PV reaches 100 °C, the temperature is kept
for 10 minutes. after 10 minutes alarm1 and control function are turned OFF
Parameter setting
Level
Parameter
Set value
Description
1
SV
100.0
Target temperature
3
ALD1
m
r
a
l
a
k
a
o
s
s
a
1
L
A
0
1
1
SOAK(AL1)
00.10
10 minute temperature maintain
Temperature
Time up
Alarm=OFF
100.0
PV
Temperature rise
25.0
Alarm=ON
PV time chart
time
5
SOAK
10 minutes
seconds
Action
ON
AL1 time chart OFF
time