tae TA-100/6P Instruction And Operation Manual Download Page 5

5

missprints and technical changes reserved

Instruction & Operating Manual

TA-15/6P...200/6P

5.1 Armature feedback control (UA-controlled)

1)

Jumper 

VI

 must be installed if a controlled decelaration at drive stop is requested. For 

Emergency

off 

the connection between terminals 24 and 25 must be opened (Quick-stop). The drive will be

locked immidiately.

2)

Check all connections with an Ohm-meter for grounds.

3)

Install jumpers 

I

 and 

VII

 and also resistor R82 (22 KOhm).

4)

Check if line voltage corresponds with voltage indicated on the type marking. Select applicable

frequency, 50 Hz or 60 Hz with frequency-switch.

5)

Switch on line voltage. The following LED must light up:

LED 8

green

Line on

LED 5

green

+15V

LED 2

green

-15V

The diodes LED 4 (red) and the six diodes LED 1 (clear) will only light up briefly.

6)

Measure field voltage at terminal F+ and F- with a Multimeter (moving coil meter with at least 330

Ohm/Volt) 270V at 400V or 155V at 230V line-voltage. Measure voltage at potentiometer  (terminal

5- and 6+) 10 V d.c. Set min. speed potentiometer during this measurement fully counter

clockwise.

7)

Potentiometer P4

Acceleration time, set in center position

Potentiometer P2

Deceleration time, set in center position

Potentiometer P3

IxR Compensation, set fully counter clockwise

Potentiometer P8

Stability, set in center position

Potentiometer P7

Jog speed, set fully counter clockwise

Potentiometer P10

Delay time, set fully clockwise

8)

Switch on the drive, LED 11 yellow (Drive on) and LED 9, green (drive release) will light up. When

the speed potentiometer is turned in clockwise direction, the armature voltage and the motor

speed respectively, will increase. This causes the six clear diodes LED 1 (Thyristor triggering) to

light up. Adjust potentiometer P9 (max. speed) for the requested armature voltage/motor speed.

Now set speed potentiometer fully counter clockwise, the output voltage must drop back to 0V.

Now adjust potentiometer P6 for the requested minimum speed.

9)

Switch off drive, Jog speed switch on.(LED 7 and LED 9 will light up). Adjust the requested jog

speed with potentiometer P7 (Jog speed).

10)

Adjust I x R compensation. Check for an apoprox equal speed with and without motor load in the

lower speed range. If the potentiometer is turned in clockwise direction the speed under load will

increase.

If the compensation potentiometer is set too high, the drive will become unstable.

Caution!

Do not use 

any

 Mega-Ohm-meter, buzzer or similar test instruments.

Test instruments must be galvanically seperated from a.c. line.

5.

Functional tests and preliminary adjustments before operation

Summary of Contents for TA-100/6P

Page 1: ...antriebstechnik de TA_BA TA 15 200_6P_EN PDF The German text applies in cases of doubt TA 15 6P 200 6P Instruction and Operation Manual Caution There is always a risk involved in the handling of electrical machinery Therefore mounting and maintenance should only be done by authorized personnel ...

Page 2: ...nal 4 and 9 Jog Speed ON Closing contact Drive remains switched on until contacts open 1 Technical Data r Motor Zero Speed Indicator r Current Limit control r Tachometer Signal control r Electronic circuit galvanically seperated from line when tachometer feedback is utilized Drive Type TA 15 6P TA 40 6P TA 60 6P TA 100 6P TA 200 6P Line Voltage 230VAC 400VAC 230VAC 400VAC 230VAC 400VAC 230VAC 400V...

Page 3: ...tor speed r When tachometer feedback is utilized jumpers I and VII and resistor R82 must be removed r Jumpers IX and X must be installed and jumper VIII must be removed r The adaption of the tachometer signal is achived by changing the value of resistor R91 Terminal 11 and 20 Terminals for connection of d c tachometer KL 11 Negative KL 20 Positive r Jumpers IX and X must be removed and jumper VIII...

Page 4: ...s installed or when the reference speed is changed Current limit P5 Adjustment of the requested max armature current adjust the nominal motor current Minimum Speed P6 Adjustment of min speed during operation set potentiometer fully counter clockwise Jog speed P7 Speed adjustment for jog speed Stability P8 Adjustment for the dynamical adaption to the load Maximum speed P9 Adjustment of max speed du...

Page 5: ...n center position Potentiometer P3 IxR Compensation set fully counter clockwise Potentiometer P8 Stability set in center position Potentiometer P7 Jog speed set fully counter clockwise Potentiometer P10 Delay time set fully clockwise 8 Switch on the drive LED 11 yellow Drive on and LED 9 green drive release will light up When the speed potentiometer is turned in clockwise direction the armature vo...

Page 6: ...tiometer P8 This potentiometer must be adjusted so that the drive operates without overshoot in the presset speeds 5 2 Tachometer feedback control 1 Check all connections with an Ohm meter for grounds 2 Install required jumpers for tachometer feedback control depending if a c or d c tachometer is used see page 2 terminals 19 and 20 or 11 and 20 respectively 3 Remove resistor R82 and also remove ju...

Page 7: ...ctive fuse Si 1 on the upper PC board c LED 8 Power on does not light up d LED 9 does not light up however LED 11 lights up jumper or quick stop contacts terminals 24 and 25 not closed e No reference voltage terminal 2 voltage is variable by speed potentiometer from 0 to 10V f Relay d6 malfunction not energised LED 3 red lights up Confirmation of malfunction is only possible if LED 4 and LED 6 do ...

Page 8: ...l Type TA 15 6P 200 6P a Too low adjustment of current limit b Motor is overloaded mechanical defect on machine or motor Check motor brushess c Supply voltage 15V for electronic circuit incorrect or missing Reference voltage 10V incorrect or missing Check LED 5 and LED 2 d Triggering of one Thyristor temporarely interrupted Defective tachometer or tachometer leads Defective minimum speed potentiom...

Page 9: ...R VITESSE D ACCROCHAGE Reglerfreigabe ALTERNATIF FIELD DC TACHOMETER Sollwertpotentiometer Schleichgang JOG SPEED DEBLOCAGE RUN EXCITATION Feld Anker Netz INDUIT ARMATURE ALIMENTATION EN LINE FAULT DOCKET Störmeldung G d2 E d1 S B2 E1 F1 A1 M Starting at TA 60 6P ab TA 60 6P Only by TA 40 6P availble Nur bei TA 40 6P vorhanden Strom Istwert 15V CURRENT FEEDBACK 24 L1 N 25 4 Kl 2 3 23 22 21 20 19 1...

Page 10: ...changes reserved Instruction Operating Manual TA 15 6P 200 6P 8 Mounting template TA 40 6P TA 60 6P 200 6P TA 15 6P 310 270 165 7 x 13 270 350 KL1 310 270 165 7 x 13 400 270 460 40 KL3 KL1 KL2 530 486 ø10 5 250 12 486 510 KL3 KL1 ...

Reviews: