Instruction & Operating Manual

TA-15/6P...200/6P

Terminal 7 and 8

Terminals for contacts of all malfunction signals. (Contacts open in event of fault)

Terminal 2, 5, 6

Speed potentiometer

With this potentiometer the speed is infinite variable from minimum to maximum

speed.
Poti-connect: KL. 5 = Beginning

KL. 6 = End

KL. 2 = Connect center

Terminal 13

Current reference signal output

Terminal 18

Current reference signal input

Terminal 13 and 18

For speed control these terminals must be jumpered

Terminal 17

Reference signal (negative) 0-max. 200V

depending on value of resistor R83

General input voltage 0-10V

Terminal 19 and 20

Terminals for connection of a.c. tachometer

Output voltage of tachometer approximately 100-150V at rated motor speed.

r

When tachometer feedback is utilized jumpers 

I

 and 

VII

 and resistor R82 must

be removed.

r

Jumpers 

IX

 and 

X

 must be installed and jumper 

VIII

 must be removed.

r

The adaption of the tachometer signal is achived by changing the value of

resistor R91.

Terminal 11 and 20

Terminals for connection of d.c. tachometer
KL. 11 = Negative
KL. 20 = Positive

r

Jumpers 

IX

 and 

X

 must be removed and jumper 

VIII

 must be installed.

r

The adaption of the tachometer signal is achieved by changing the value of

resistor R91.
R91 is calculated as follows:
R91 in kOhm = tachometer voltage at rated motor speed minus 50

Terminal 22 and 23

Relay contacts (normally open, no potential)

(for operation of auxiliary armature solenoid.)

Terminal 24 and 25

Terminals for quick-stop (normally closed)

Terminal L1 and N

Terminals for connection of fan 230V VAC, 50/60Hz at TA-60/6P

2.3 Terminal Strip KL. 2

 (Only at TA-40/6P available)

Terminal 3 and 4

Terminals for connection of fan 230V VAC, 50/60Hz

Summary of Contents for TA-100/6P

Page 1: ...antriebstechnik de TA_BA TA 15 200_6P_EN PDF The German text applies in cases of doubt TA 15 6P 200 6P Instruction and Operation Manual Caution There is always a risk involved in the handling of electrical machinery Therefore mounting and maintenance should only be done by authorized personnel ...

Page 2: ...nal 4 and 9 Jog Speed ON Closing contact Drive remains switched on until contacts open 1 Technical Data r Motor Zero Speed Indicator r Current Limit control r Tachometer Signal control r Electronic circuit galvanically seperated from line when tachometer feedback is utilized Drive Type TA 15 6P TA 40 6P TA 60 6P TA 100 6P TA 200 6P Line Voltage 230VAC 400VAC 230VAC 400VAC 230VAC 400VAC 230VAC 400V...

Page 3: ...tor speed r When tachometer feedback is utilized jumpers I and VII and resistor R82 must be removed r Jumpers IX and X must be installed and jumper VIII must be removed r The adaption of the tachometer signal is achived by changing the value of resistor R91 Terminal 11 and 20 Terminals for connection of d c tachometer KL 11 Negative KL 20 Positive r Jumpers IX and X must be removed and jumper VIII...

Page 4: ...s installed or when the reference speed is changed Current limit P5 Adjustment of the requested max armature current adjust the nominal motor current Minimum Speed P6 Adjustment of min speed during operation set potentiometer fully counter clockwise Jog speed P7 Speed adjustment for jog speed Stability P8 Adjustment for the dynamical adaption to the load Maximum speed P9 Adjustment of max speed du...

Page 5: ...n center position Potentiometer P3 IxR Compensation set fully counter clockwise Potentiometer P8 Stability set in center position Potentiometer P7 Jog speed set fully counter clockwise Potentiometer P10 Delay time set fully clockwise 8 Switch on the drive LED 11 yellow Drive on and LED 9 green drive release will light up When the speed potentiometer is turned in clockwise direction the armature vo...

Page 6: ...tiometer P8 This potentiometer must be adjusted so that the drive operates without overshoot in the presset speeds 5 2 Tachometer feedback control 1 Check all connections with an Ohm meter for grounds 2 Install required jumpers for tachometer feedback control depending if a c or d c tachometer is used see page 2 terminals 19 and 20 or 11 and 20 respectively 3 Remove resistor R82 and also remove ju...

Page 7: ...ctive fuse Si 1 on the upper PC board c LED 8 Power on does not light up d LED 9 does not light up however LED 11 lights up jumper or quick stop contacts terminals 24 and 25 not closed e No reference voltage terminal 2 voltage is variable by speed potentiometer from 0 to 10V f Relay d6 malfunction not energised LED 3 red lights up Confirmation of malfunction is only possible if LED 4 and LED 6 do ...

Page 8: ...l Type TA 15 6P 200 6P a Too low adjustment of current limit b Motor is overloaded mechanical defect on machine or motor Check motor brushess c Supply voltage 15V for electronic circuit incorrect or missing Reference voltage 10V incorrect or missing Check LED 5 and LED 2 d Triggering of one Thyristor temporarely interrupted Defective tachometer or tachometer leads Defective minimum speed potentiom...

Page 9: ...R VITESSE D ACCROCHAGE Reglerfreigabe ALTERNATIF FIELD DC TACHOMETER Sollwertpotentiometer Schleichgang JOG SPEED DEBLOCAGE RUN EXCITATION Feld Anker Netz INDUIT ARMATURE ALIMENTATION EN LINE FAULT DOCKET Störmeldung G d2 E d1 S B2 E1 F1 A1 M Starting at TA 60 6P ab TA 60 6P Only by TA 40 6P availble Nur bei TA 40 6P vorhanden Strom Istwert 15V CURRENT FEEDBACK 24 L1 N 25 4 Kl 2 3 23 22 21 20 19 1...

Page 10: ...changes reserved Instruction Operating Manual TA 15 6P 200 6P 8 Mounting template TA 40 6P TA 60 6P 200 6P TA 15 6P 310 270 165 7 x 13 270 350 KL1 310 270 165 7 x 13 400 270 460 40 KL3 KL1 KL2 530 486 ø10 5 250 12 486 510 KL3 KL1 ...