Instruction & Operating Manual
TA-15/6P...200/6P
Terminal 7 and 8
Terminals for contacts of all malfunction signals. (Contacts open in event of fault)
Terminal 2, 5, 6
Speed potentiometer
With this potentiometer the speed is infinite variable from minimum to maximum
speed.
Poti-connect: KL. 5 = Beginning
KL. 6 = End
KL. 2 = Connect center
Terminal 13
Current reference signal output
Terminal 18
Current reference signal input
Terminal 13 and 18
For speed control these terminals must be jumpered
Terminal 17
Reference signal (negative) 0-max. 200V
depending on value of resistor R83
General input voltage 0-10V
Terminal 19 and 20
Terminals for connection of a.c. tachometer
Output voltage of tachometer approximately 100-150V at rated motor speed.
r
When tachometer feedback is utilized jumpers
I
and
VII
and resistor R82 must
be removed.
r
Jumpers
IX
and
X
must be installed and jumper
VIII
must be removed.
r
The adaption of the tachometer signal is achived by changing the value of
resistor R91.
Terminal 11 and 20
Terminals for connection of d.c. tachometer
KL. 11 = Negative
KL. 20 = Positive
r
Jumpers
IX
and
X
must be removed and jumper
VIII
must be installed.
r
The adaption of the tachometer signal is achieved by changing the value of
resistor R91.
R91 is calculated as follows:
R91 in kOhm = tachometer voltage at rated motor speed minus 50
Terminal 22 and 23
Relay contacts (normally open, no potential)
(for operation of auxiliary armature solenoid.)
Terminal 24 and 25
Terminals for quick-stop (normally closed)
Terminal L1 and N
Terminals for connection of fan 230V VAC, 50/60Hz at TA-60/6P
2.3 Terminal Strip KL. 2
(Only at TA-40/6P available)
Terminal 3 and 4
Terminals for connection of fan 230V VAC, 50/60Hz