11 Service and Maintenance

The pump is nearly free of maintenance. If the pump was not working for 
a longer time or the system is heavily contaminated could the rotor be blocked. 
It will shown by flashing of three LED lights.
By removing of he motor head ( loosening the union nut and remove the motor 
head ) the impeller is accessible and can be also removed. By doing this the blo-
ckade can be solved and / or the pump can be cleaned.
Tighten the union nut with 30 Nm torque.

 maintenance, cleaning 

or repair work, and secure it against unauthorised reactivation.
Allow the pump to cool down in the event of high temperatures and system
pressures. There is a 

risk of scalds!

12 Faults, Causes and Remedies

Maintenance work or repair attempts may only be undertaken by qualified persons.

 maintenance, cleaning or repair work,

and secure it against unauthorised reactivation. Allow the pump to cool down in the event of
high temperatures and system pressures. 

There is a risk of scalds!

Please contact a specialist technician should it not be possible to eliminate the fault.

Error indication or
Error code in the display
of the pump

The pump does not supply
display does no lit

The pump is running but no
water will be supplied
Noises in the system

The three LED's are flashing
twice
the pump will try to start
again
All three LED's are flashing  

possible causes

faulty voltage supply

Air in the system
Valve closed
Air in the system
Capacity of the pump too high
Rotor blocked

overtemperature

electronic error

remedy

check the power supply
If necessary, switch on the protective switch again.
Voltage reset necessary - disconnect the pump from
the power supply and wait approx. 1 minute
Is the error still existing the pump must be replaced
bleed the system  ( see chapter 10 in the manual )
Open the Valve
bleed the system  ( see chapter 10 in the manual )
check the pump settings
Maintenance necessary ( see chapter 11 in the 
manual )
Is the error still existing the pump must be replaced

sink the temperature in the system
Press any key or disconnect the pump for minimum 
1 minute from the power supply
Is the error still existing the pump must be replaced
replace the pump

Summary of Contents for TACOFLOW2 PURE 15

Page 1: ...MATION TACONOVA COM Taconova Group AG Neunbrunnenstrasse 40 CH 8050 Zurich T 41 44 735 55 55 F 41 44 735 55 02 group taconova com V1 10 2019 215347 EA Nr 1298 INSTALLATION AND OPERATING INSTRUCTIONS D...

Page 2: ...beiten 6 2 6 Sicherheitshinweise f r den Betreiber 6 2 7 Sicherheitshinweise f r Montage und Wartungsarbeiten 7 2 8 Eigenm chtiger Umbau und Ersatzteilherstellung 7 2 9 Unzul ssige Betriebsweisen 8 3...

Page 3: ...er name type or model lot batch or serial number nom type ou modele no de lot d echantillon ou de serie auf das sich diese Erkl rung bezieht mit der den folgenden Norm en oder normativen Dokument en b...

Page 4: ...ty instructions listed under section 2 and the special safety instructions detailed in the other sections A copy of the EC Declaration of Conformity is provided with these instructions This declaratio...

Page 5: ...relevant qualifications Areas of responsibility and monitoring of personnel must be guaranteed by the owner operator If personnel do not have the necessary know how they must be trained or instructed...

Page 6: ...aping fluids resulting from a leak Failure of prescribed repair and maintenance work 2 5 Safety conscious working Observe the safety instructions detailed in this manual along with the current nationa...

Page 7: ...These persons must also have familiarised themselves in advance with the product using the operating instructions Conducting work on the pump is only permitted when the system is shut down Ensure tha...

Page 8: ...observe section 4 of these operating instructions here Ensure compliance with the limit values detailed in the technical data 3 Transport and Storage After receiving the product inspect it immediately...

Page 9: ...ungsaufnahme P1 W Versorgungsspannung Emissions Schalldruckpegel Schutzart W rmeklasse Umgebungstemperatur Medientemperatur Systemdruck Max Zugelassene F rdermedien Kennlinie TacoFlow2 PURE 15 10 65 m...

Page 10: ...dard pumps The pump can reduce energy consumption by up to 80 compared to a standard circulation pump whilst maintaining the same level of hydraulic power 7 Pump Settings and Output After connecting o...

Page 11: ...culation pump whilst maintaining the same level of hydraulic power 7 Pump Settings and Output After connecting of the pump with the power supply LED lights on the control panel are showing the selecte...

Page 12: ...s of local energy supplier Observe accident prevention regulations Never pull on the power cable Do not bend the cable Do not place any objects on the cable When using the pump in systems at temperatu...

Page 13: ...system correctly To vent the pump loosen the indicated screw by turning it anti clockwise Caution Hot water may escape here depending on the system s operating state Then tighten the union nut with 3...

Page 14: ...nd system pressures There is a risk of scalds Please contact a specialist technician should it not be possible to eliminate the fault Error indication or Error code in the display of the pump The pump...

Page 15: ...not dispose of the pump and or individual parts in household waste Dispose of the pump and or parts in an environmentally conscious way To do this please contact a public or private disposal organisa...

Page 16: ...CONTACT AND FURTHER INFORMATION TACONOVA COM Taconova Group AG Neunbrunnenstrasse 40 CH 8050 Zurich T 41 44 735 55 55 F 41 44 735 55 02 group taconova com V1 10 2019 215347 EA Nr 1298...

Reviews: