Fault description
Cause
Remedy
Personnel
Flow rate is not measured,
although fresh water is
flowing.
Flow sensor for
fresh water is dirty
or defective.
Clean or replace the flow sensor.
Electrician
Circuit board defec-
tive.
9.4.2 ‘Replacing the circuit board’
36).
Electrician
Wiring faulty.
Check the wiring and replace it, if
necessary.
Electrician
9.4
Work required for repairing faults
9.4.1
Work required for repairing faults on the heat interface unit
When performing work required to repair faults
affecting the heat interface unit, observe the oper-
ating instructions for the heat interface unit
Chapter 1.2 ‘Other applicable documents’
9.4.2
Replacing the circuit board
Personnel:
n
Electrician
1.
Save the set parameters externally (service personnel only).
2.
Disconnect the connector from the socket.
3.
Unplug the LAN cable and USB cable.
4.
Remove the screws in the controller box to open the controller
box.
5.
Unplug the terminal plugs from the terminal strips on the circuit
board.
6.
Remove the circuit board.
7.
Insert a new circuit board and click it into place.
8.
Plug the terminal plugs into the terminal strips on the circuit
board.
9.
Close the controller box and screw it together.
10.
Connect the HMI to the controller (
25).
11.
Connect the connector to the socket.
12.
Chapter 6.2.1 ‘Setting parameters on
25) or load them using a USB stick (service per-
sonnel only).