Taco PC702–1 Instruction Sheet Download Page 8

8 of 8 

The installer must ensure that this control and its wiring are isolated and/or shielded from strong sources of electromagnetic noise. 
Conversely, this Class B digital apparatus complies with Part 15 of the FCC Rules and meets all requirements of the Canadian 
Interference-Causing Equipment Regulations. However, if this control does cause harmful interference to radio or television reception, 
which can be determined by turning the control off and on, the user is encouraged to try to correct the interference by reorienting or 
relocating the receiving antenna, relocating the receiver with respect to this control, and/or connecting the control to a different circuit 
from that to which the receiver is connected. 

PC702-1 Two Stage Boiler Reset & DHW Control

 

Control — 

Microprocessor PI control; This is 

not a safety (limit) control

Packaged weight 

—  1.5 lb. (670 g) 

Dimensions — 

4-3/4” H x 2-7/8” W x 7/8” D (120 x 74 x 22 mm) 

Approvals — 

CSA 

NRTL 

/C; Meets ICES & FCC regulations for EMI/RFI. 

Ambient conditions 

—  Indoor use only, 32 to 105

°

F (0 to 40

°

C), < 90% RH non- 

condensing. 

Power supply 

—  Class 2, 24 V 

±

10% 50/60 Hz 3 VA (Powered by Taco -Exp 

Control) 

Relays — 

24 

(ac) 5 A 1/6 hp, pilot duty 240 VA 

DHW Demand 

—  20 to 260 V (ac) 2 VA 

Sensors — 

NTC thermistor, 10 k

 @ 77

°

F (25

°

±

0.2

°

C) ß=3892 

included: 

Outdoor Sensor M 2036 and Universal Sensor 071. 

Factory 

Boiler Start

 

—  35 to 150

°

F (2 to 66

°

C) 70

°

F (21

°

C) 

Outdoor Start

 

  35 to 85

°

F (2 to 29

°

C) 70

°

F (21

°

C) 

Boiler Design

 

  70 to 220

°

F (21 to 104

°

C) 

190

°

F (88

°

C) 

Outdoor Design

 

  -60 to 32

°

F (-51 to 0

°

C) 10

°

F (-12

°

C) 

Boiler

 

Minimum

 

— Off, 80 to 180

°

F (Off, 27 to 82

°

C) 

140

°

F (60

°

C) 

Differential

 

—  Auto, 2 to 42

°

F (Auto, 1 to 24

°

C) 

Auto 

Interstage Delay

 

—  0:30 to 4:00 minutes 

2:00 min. 

WWSD

 

—  35 to 100

°

F, Off (2 to 38

°

C, Off) 

70

°

F (21

°

C) 

Units

 

— 

°

F, 

°

°

Do It Once. Do It Right.

 

TACO, INC.

, 1160 Cranston Street, Cranston, RI 02920 

Telephone: (401) 942-8000 

FAX: (401) 942-2360. 

TACO (Canada), Ltd.

, 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 

905/564-9436. 

Visit our web site at:

 http://www.taco-hvac.com 

Copyright 2004 TACO, Inc. 

Portions Copyright 2000 

tekmar Control Systems Ltd. 

tekmar Control Systems Inc. 

STEP SIX

 

• Install the wiring cover over the wiring chamber and secure it with the screw provided. 

• Place the front cover on the control and snap it into place. 

• It is important to explain the operation of this control within the system to the end user, and to anyone else who may be operating 

the system. 

Error Messages

Whenever a fault is detected, an error message will be displayed to indicate the location of the problem. 

OUTDR

OUTDR

BOIL

BOIL

EEPROM

Read Error

Outdoor

Sensor Short

Circuit

Outdoor

Sensor Open

Circuit

Boiler

Sensor Short

Circuit

Boiler

Sensor Open

Circuit

Refer to the troubleshooting section

for operation details.

Item

1

H1

192A

Power:

24 V 

±

10% 50/60 Hz 3 VA

Relays:

120 V (ac) 5 A 1/6 hp pilot 240 VA

Demand:

20 to 260 V (ac) 2 VA

Jul 00

31000265

Press & Hold:

Item, to view settings

, to test

Press & Release:

Item +   +   to adjust menu

2

3

®

Signal wiring

must be rated

at least 300V

Made in
Canada

PC702-1

4

5

6

7

Com Sup Out

Do not apply power

Rotation On / Of

f

Boiler

Demand

DHW

Demand

Interstage

Delay

Start

Stage
1      1

Stage
2      2

C

US

158033

OUTDR

°

F

1 2

VIEW

Technical Data

Summary of Contents for PC702–1

Page 1: ...portional to the temperature of the supplywaterandthesurfaceareaoftheheatingelement Asmallsurface area such as baseboard radiators requires a higher water temperature than a larger surface area such as radiant floors The heat lost from a building is dependent on the outdoor temperature as well as other factors As the outdoor temperature drops the building heat loss increases InstructionSheet PC702...

Page 2: ...iler jacket losses Differential An on off boiler must be operated with a differential in order to prevent short cycling When the supply water temperature drops below the bottom rail of the differential the boiler is turned on The boiler is then kept on until the supply water temperature rises above the top rail of the differential If the differential is too wide there can be large supply watertemp...

Page 3: ...iler setting This pro grammed function has an OFF setting for condensing and electric boilers When operating at the minimum setting the control displays the MIN segment in the LCD when either that boiler supply or boiler target temperature are being viewed ROTATION The PC702 1 has an optional boiler rotation function that is selected using the DIP switch located next to terminal 1 in the wiring ch...

Page 4: ...the sensor cover off by sliding it upward relative to the sensor base Use one round or pan head screw to attach the base of the sensor to the wall The sensor is wall mounted and the wiring enters through the bottom of the enclosure The hole for the cable entry must face downward in order to prevent water from entering and filling the enclosure The sensor should be mounted on a wall which best repr...

Page 5: ... be adjusted from 35 to 150 F 2 to 66 C This setting is typically set to the desired building temperature In applications where fan coils are used the BOIL Start may need to be set higher to prevent cold drafts during mild outdoor conditions If the building feels cool during mild outdoor conditions the BOIL Start setting should be increased Outdoor Starting Temperature OUTDR Start The OUTDR Start ...

Page 6: ...esign __________________________________ WWSD ______________________________________ Differential Example 10 F 6 C Btu hr input 100 000 Btu hr System US GPM x 500 20 US GPM x 500 ADJUST MENU To enter the adjustment mode Press and Hold simultaneously the Item and Buttons The ADJUST element will turn on Start Interstage Delay DHW Demand Boiler Demand BOIL F ADJUST Start Interstage Delay DHW Demand B...

Page 7: ... not be connected to the control while the test is performed Using the chart below estimate the temperature measured by the sensor The sensor and thermometer readings should be close If the test meter reads a very high resistance there may be a broken wire a poor wiring connection or a defective sensor If the resistance is very low the wiring may be shorted theremaybemoistureinthesensororthesensor...

Page 8: ...or Design 60 to 32 F 51 to 0 C 10 F 12 C Boiler Minimum Off 80 to 180 F Off 27 to 82 C 140 F 60 C Differential Auto 2 to 42 F Auto 1 to 24 C Auto Interstage Delay 0 30 to 4 00 minutes 2 00 min WWSD 35 to 100 F Off 2 to 38 C Off 70 F 21 C Units F C F Do It Once Do It Right TACO INC 1160 Cranston Street Cranston RI 02920 Telephone 401 942 8000 FAX 401 942 2360 TACO Canada Ltd 6180 Ordan Drive Missis...