background image

7 of 8 

Troubleshooting

STEP FIVE

 

As in any troubleshooting procedure, it is important to isolate a problem as much as possible before proceeding. The error messages 
greatly simplify troubleshooting of the PC702-1. When the control displays an error message, identify the fault from the look-up table 
on page 8 and follow standard testing procedures to confirm the problem. If you suspect a wiring fault, return to step three and carefully 
check all external wiring and wiring connections. 

Sensor and Internal Faults

 

•  If an outdoor sensor fault occurs, the PC702-1 will assume a fixed outdoor temperature of 32

°

F (0

°

C) and will target the appropriate 

supply water temperature. An error message is displayed. 

• If a supply sensor fault occurs, the PC702-1 turns the boiler off and displays an error message. 

• If an EEPROM fault occurs, the PC702-1 turns the boilers off until all the settings are checked. 

Adjustment of Settings

 

• If the outdoor temperature is cold and the rooms are cold, increase the BOIL DSGN setting by 5

°

F (3

°

C) per day. 

• If the outdoor temperature is near the WWSD temperature and the rooms are cold, increase the BOILStart setting. 

• If the boiler is cycling too often, increase the Differential setting or set control to Ad (Auto Differential). If the second stage is coming 
on too soon, increase the Interstage Delay setting. 

Testing the Sensors

 

A good quality test meter capable of measuring up to 5,000 k

  (1 k

 = 1000 

) is required 

to measure the sensor resistance. In addition to this, the actual temperature must be 
measured with either a good quality digital thermometer, or, if a thermometer is not 
available, a second sensor can be placed alongside the one to be tested and the readings 
compared. 
First measure the temperature using the thermometer and then measure the resistance 
of the sensor at the control. The wires from the sensor must not be connected to the 
control while the test is performed. Using the chart below, estimate the temperature 
measured by the sensor. The sensor and thermometer readings should be close. If the 
test meter reads a very high resistance, there may be a broken wire, a poor wiring 
connection or a defective sensor. If the resistance is very low, the wiring may be shorted, 
there may be moisture in the sensor or the sensor may be defective. To test for a defective 
sensor, measure the resistance directly at the sensor location. 

Do not apply voltage to a sensor at any time as damage to the sensor may result.

 

Temperature

Resistance

Temperature

Resistance

Temperature

Resistance

Temperature

Resistance

°

F

°

C

°

F

°

C

°

F

°

C

°

F

°

C

-30

-20

-10

0

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

190

200

-34

-29

-23

-18

-12

-7

-1

4

10

16

21

27

32

38

43

49

54

60

66

71

77

82

88

93

234,196

165,180

118,018

85,362

62,465

46,218

34,558

26,099

19,900

15,311

11,883

9,299

7,334

5,828

4,665

3,760

3,050

2,490

2,045

1,689

1,403

1,172

983

829

POWER UP

Start

Interstage

Delay

DHW

Demand

Boiler

Demand

Start

Interstage

Delay

DHW

Demand

Boiler

Demand

Start

Interstage

Delay

DHW

Demand

Boiler

Demand

Start

Interstage

Delay

DHW

Demand

Boiler

Demand

Start

Interstage

Delay

DHW

Demand

Boiler

Demand

Outdoor
Temperature

The OUTDR element
is turned on. The
outdoor temperature
is displayed

Boiler
Temperature

Press and release
the 

Item

 button. The

boiler supply
temperature is
displayed.

Boiler Target
Temperature

Press and release
the 

Item

 button. The

boiler target
temperature is
displayed.

VIEW MENU

On power up, the
control displays all
segments for 2
seconds and the
control version
number.

The control then
automatically goes
to operating mode,
and displays the
outdoor
temperature.

To view all control settings, the 

Item

 button

may be pressed and held while in the View
Menu. The control will then scroll through all
the adjustable items.

OUTDR

°

F

TARGET

DSGN DIFF

BOIL

OUTDR

WWSD

°

F

°

C

1 2

MAX

MIN

OUTDR

°

F

1 2

BOIL

°

F

1 2

TARGET

BOIL

°

F

1 2

VIEW

VIEW ADJUST

VIEW

VIEW

VIEW

Summary of Contents for PC702–1

Page 1: ...portional to the temperature of the supplywaterandthesurfaceareaoftheheatingelement Asmallsurface area such as baseboard radiators requires a higher water temperature than a larger surface area such as radiant floors The heat lost from a building is dependent on the outdoor temperature as well as other factors As the outdoor temperature drops the building heat loss increases InstructionSheet PC702...

Page 2: ...iler jacket losses Differential An on off boiler must be operated with a differential in order to prevent short cycling When the supply water temperature drops below the bottom rail of the differential the boiler is turned on The boiler is then kept on until the supply water temperature rises above the top rail of the differential If the differential is too wide there can be large supply watertemp...

Page 3: ...iler setting This pro grammed function has an OFF setting for condensing and electric boilers When operating at the minimum setting the control displays the MIN segment in the LCD when either that boiler supply or boiler target temperature are being viewed ROTATION The PC702 1 has an optional boiler rotation function that is selected using the DIP switch located next to terminal 1 in the wiring ch...

Page 4: ...the sensor cover off by sliding it upward relative to the sensor base Use one round or pan head screw to attach the base of the sensor to the wall The sensor is wall mounted and the wiring enters through the bottom of the enclosure The hole for the cable entry must face downward in order to prevent water from entering and filling the enclosure The sensor should be mounted on a wall which best repr...

Page 5: ... be adjusted from 35 to 150 F 2 to 66 C This setting is typically set to the desired building temperature In applications where fan coils are used the BOIL Start may need to be set higher to prevent cold drafts during mild outdoor conditions If the building feels cool during mild outdoor conditions the BOIL Start setting should be increased Outdoor Starting Temperature OUTDR Start The OUTDR Start ...

Page 6: ...esign __________________________________ WWSD ______________________________________ Differential Example 10 F 6 C Btu hr input 100 000 Btu hr System US GPM x 500 20 US GPM x 500 ADJUST MENU To enter the adjustment mode Press and Hold simultaneously the Item and Buttons The ADJUST element will turn on Start Interstage Delay DHW Demand Boiler Demand BOIL F ADJUST Start Interstage Delay DHW Demand B...

Page 7: ... not be connected to the control while the test is performed Using the chart below estimate the temperature measured by the sensor The sensor and thermometer readings should be close If the test meter reads a very high resistance there may be a broken wire a poor wiring connection or a defective sensor If the resistance is very low the wiring may be shorted theremaybemoistureinthesensororthesensor...

Page 8: ...or Design 60 to 32 F 51 to 0 C 10 F 12 C Boiler Minimum Off 80 to 180 F Off 27 to 82 C 140 F 60 C Differential Auto 2 to 42 F Auto 1 to 24 C Auto Interstage Delay 0 30 to 4 00 minutes 2 00 min WWSD 35 to 100 F Off 2 to 38 C Off 70 F 21 C Units F C F Do It Once Do It Right TACO INC 1160 Cranston Street Cranston RI 02920 Telephone 401 942 8000 FAX 401 942 2360 TACO Canada Ltd 6180 Ordan Drive Missis...

Reviews: