background image

5 of 8 

STEP THREE

 

Wiring to the Zone Control

 

Connect the PC702-1 cable to the Add-On interface on the Taco Zone Control. Ensure the 

Mode

 switch on the Zone Control is set 

to 

Reset

Wiring the Sensors

 

Do not apply power to these terminals as this will damage the control.

 

Outdoor Sensor

 

Connect the two wires from the Outdoor Sensor to the terminals 

Com 

— 

Out 

 (5 and 

7). The Outdoor Sensor measures the outdoor air temperature. 

Boiler Sensor

 

Connect the two wires from the Boiler Sensor to the terminals 

Com — Sup

 (5 and 6). 

The Boiler Sensor measures the supply water temperature going from the boiler to the 
system. 

Wiring the Boilers

 

The Stage 1 and Stage 2 terminals (1 & 2 and 3 & 4) are isolated outputs in the PC702-1. 
There is no power available on these terminals from the control. These terminals are to 
be used as a switch to either make or break the boiler circuit. When the PC702-1 requires 
the boiler(s) to fire, it closes the contact between terminals 1 and 2 and/or 3 and 4. 

DHW Demand

 

To generate a DHW demand, a voltage between 24 and 240 V(ac) must be applied across 
the two DHW demand wires (black wires) coming from the back of the control. This can 
be achieved by wiring these two wires in parallel to the DHW (priority) zone on the Taco 
Zone Control. 

Settings

Before adjusting the settings, read through the sequence of operation to ensure that you understand how the control operates. The 
following page describes how to program these settings into the control once it has been powered up. 

STEP FOUR

 

Boiler Starting Temperature (BOIL Start)

 

The 

BOIL Start

 setting is the starting supply water temperature of the reset ratio, and can be adjusted from 35 to 150

°

F (2 to 66

°

C). 

This setting is typically set to the desired building temperature. In applications where fan coils are used, the 

BOIL Start

 may need to 

be set higher to prevent cold drafts during mild outdoor conditions. If the building feels cool during mild outdoor conditions, the BOIL 
Start setting should be increased. 

Outdoor Starting Temperature (OUTDR Start)

 

The OUTDR Start setting is the outdoor temperature at which the starting temperature is supplied. The adjustment range is from 35 
to 85 

°

F (2 to 29

°

C). This setting is typically set to the desired building temperature. 

Boiler Design Temperature (BOIL DSGN)

 

The BOIL DSGN setting is the water temperature required to satisfy the building heat loss during the coldest outdoor temperature. 
This adjustment is typically dependent on the type of heating terminal used. The following are suggested settings for different terminal 
units: 

• Inslab Radiant  .....................  100 to 140

°

F (38 to 60

°

C) 

• Radiant Baseboard  .................  130 to 160

°

F (54 to 71

°

C) 

• Staple-up Radiant 

..........  130 to 160

°

F (54 to 71

°

C) 

• Convective Baseboard 

.......  160 to 190

°

F (71 to 88

°

C) 

• Radiators  ............................  140 to 160

°

F (60 to 71

°

C) 

• Fan Coil 

.............................. 180 

to 200

°

F (82 to 93

°

C) 

Outdoor Design Temperature (OUTDR DSGN)

 

The OUTDR DSGN setting is the outdoor temperature used in the heat loss calculation. It is set to the typical coldest outdoor 
temperature. 

Boiler Minimum Supply Temperature (BOIL MIN)

 

Most boilers require a minimum operating temperature to prevent corrosion from flue gas condensation. The 

Minimum Boiler

 setting 

should be programmed to the lowest supply water temperature at which the boiler can operate without causing the boiler flue gases 

6

Sup

5

Out

7

Com

5

Out

6

Sup

7

Com

Zone 3 Zone 4

POWER

Zone 4

Zone 3

Zone 2

INPUT

120 VOLT CIRCULATORS

STOP

Refer servicing to qualified
personnel. Opening voids
warranty

.

To DHW

Pump

Summary of Contents for PC702–1

Page 1: ...portional to the temperature of the supplywaterandthesurfaceareaoftheheatingelement Asmallsurface area such as baseboard radiators requires a higher water temperature than a larger surface area such as radiant floors The heat lost from a building is dependent on the outdoor temperature as well as other factors As the outdoor temperature drops the building heat loss increases InstructionSheet PC702...

Page 2: ...iler jacket losses Differential An on off boiler must be operated with a differential in order to prevent short cycling When the supply water temperature drops below the bottom rail of the differential the boiler is turned on The boiler is then kept on until the supply water temperature rises above the top rail of the differential If the differential is too wide there can be large supply watertemp...

Page 3: ...iler setting This pro grammed function has an OFF setting for condensing and electric boilers When operating at the minimum setting the control displays the MIN segment in the LCD when either that boiler supply or boiler target temperature are being viewed ROTATION The PC702 1 has an optional boiler rotation function that is selected using the DIP switch located next to terminal 1 in the wiring ch...

Page 4: ...the sensor cover off by sliding it upward relative to the sensor base Use one round or pan head screw to attach the base of the sensor to the wall The sensor is wall mounted and the wiring enters through the bottom of the enclosure The hole for the cable entry must face downward in order to prevent water from entering and filling the enclosure The sensor should be mounted on a wall which best repr...

Page 5: ... be adjusted from 35 to 150 F 2 to 66 C This setting is typically set to the desired building temperature In applications where fan coils are used the BOIL Start may need to be set higher to prevent cold drafts during mild outdoor conditions If the building feels cool during mild outdoor conditions the BOIL Start setting should be increased Outdoor Starting Temperature OUTDR Start The OUTDR Start ...

Page 6: ...esign __________________________________ WWSD ______________________________________ Differential Example 10 F 6 C Btu hr input 100 000 Btu hr System US GPM x 500 20 US GPM x 500 ADJUST MENU To enter the adjustment mode Press and Hold simultaneously the Item and Buttons The ADJUST element will turn on Start Interstage Delay DHW Demand Boiler Demand BOIL F ADJUST Start Interstage Delay DHW Demand B...

Page 7: ... not be connected to the control while the test is performed Using the chart below estimate the temperature measured by the sensor The sensor and thermometer readings should be close If the test meter reads a very high resistance there may be a broken wire a poor wiring connection or a defective sensor If the resistance is very low the wiring may be shorted theremaybemoistureinthesensororthesensor...

Page 8: ...or Design 60 to 32 F 51 to 0 C 10 F 12 C Boiler Minimum Off 80 to 180 F Off 27 to 82 C 140 F 60 C Differential Auto 2 to 42 F Auto 1 to 24 C Auto Interstage Delay 0 30 to 4 00 minutes 2 00 min WWSD 35 to 100 F Off 2 to 38 C Off 70 F 21 C Units F C F Do It Once Do It Right TACO INC 1160 Cranston Street Cranston RI 02920 Telephone 401 942 8000 FAX 401 942 2360 TACO Canada Ltd 6180 Ordan Drive Missis...

Reviews: