background image

The PC702-1 is a microprocessor-based control designed to regulate the supply water temperature 
from a two stage boiler system based on the outdoor temperature or DHW requirements. A wiring 
harness is provided to be easily connected to the Taco Expandable (-EXP) Controls. 

The PC702-1 includes functions such as automatic reset ratio calculation, Warm Weather Shut Down 
(WWSD), Minimum Boiler setting, adjustable interstage delay setting, optional boiler rotation, and an 
optional automatic boiler differential. The control has a digital, liquid crystal display (LCD) that nor-
mally displays the Boiler Supply temperature, but can display other temperatures and settings. 

Control Strategy  . . . . . . . . . . . .

 

pg. 1

 

Control Adjustments      . . . .   pg. 6

 

Sequence of Operation . . . . . . .

 

pg. 2

 

Troubleshooting        . . . . . . .  pg. 7

 

Installation . . . . . . . . . . . . . . . . .

 

pg. 4

 

Error Messages.  . . . . . . . . . .  pg. 8

 

Settings  . . . . . . . . . . . . . . . . . . .

 

pg. 5

 

Technical Data  . . . . . . . . . . .   pg. 8

 

Control Strategy

OUTDOOR RESET

 

In order to properly control a hot water heating system, the heat supplied 
to the building must equal the heat lost by the building. 

• The heat supplied to a building is proportional to the temperature of the 
supply water and the surface area of the heating element. A small surface 
area such as baseboard radiators requires a higher water temperature 
than a larger surface area such as radiant floors. 

• The heat lost from a building is dependent on the outdoor temperature, 
as well as other factors. As the outdoor temperature drops, the building 
heat loss increases. 

Instruction Sheet

 

PC702–1 Two Stage Boiler

 

Reset & DHW Control

 

S

UPERSEDES : 102-106, dated 

June 1, 2000 

EFFECTIVE: March 1, 2004 

Plant ID# 9300-1059 

102-106 

Constant

Room Temperature

Outdoor

Temperature

Drop

Heat
Loss

Increase

To

 Taco

Zone
Control

Item

1

H1

192A

Power:

24 V 

±

10% 50/60 Hz 3 VA

Relays:

120 V (ac) 5 A 1/6 hp pilot 240 VA

Demand:

20 to 260 V (ac) 2 VA

Jul 00

31000265

Press & Hold:

Item, to view settings

, to test

Press & Release:

Item +   +   to adjust menu

2

3

®

Signal wiring

must be rated

at least 300V

Made in
Canada

PC702-1

4

5

6

7

Com Sup Out

Do not apply power

Rotation On / Of

f

Boiler

Demand

DHW

Demand

Interstage

Delay

Start

Stage

1      1

Stage

2      2

Input

OutdoorSensor
Included

Input

Boiler Sensor
Included

DHW
Demand

C

US

158033

Output

Boiler

Output

Boiler

OUTDR

°

F

1 2

VIEW

PC702

Item

®

C

US

158033

OUTDR

°

F

VIEW

1 2

Boiler

Demand

DHW

Demand

Interstage

Delay

Start

Summary of Contents for PC702–1

Page 1: ...portional to the temperature of the supplywaterandthesurfaceareaoftheheatingelement Asmallsurface area such as baseboard radiators requires a higher water temperature than a larger surface area such as radiant floors The heat lost from a building is dependent on the outdoor temperature as well as other factors As the outdoor temperature drops the building heat loss increases InstructionSheet PC702...

Page 2: ...iler jacket losses Differential An on off boiler must be operated with a differential in order to prevent short cycling When the supply water temperature drops below the bottom rail of the differential the boiler is turned on The boiler is then kept on until the supply water temperature rises above the top rail of the differential If the differential is too wide there can be large supply watertemp...

Page 3: ...iler setting This pro grammed function has an OFF setting for condensing and electric boilers When operating at the minimum setting the control displays the MIN segment in the LCD when either that boiler supply or boiler target temperature are being viewed ROTATION The PC702 1 has an optional boiler rotation function that is selected using the DIP switch located next to terminal 1 in the wiring ch...

Page 4: ...the sensor cover off by sliding it upward relative to the sensor base Use one round or pan head screw to attach the base of the sensor to the wall The sensor is wall mounted and the wiring enters through the bottom of the enclosure The hole for the cable entry must face downward in order to prevent water from entering and filling the enclosure The sensor should be mounted on a wall which best repr...

Page 5: ... be adjusted from 35 to 150 F 2 to 66 C This setting is typically set to the desired building temperature In applications where fan coils are used the BOIL Start may need to be set higher to prevent cold drafts during mild outdoor conditions If the building feels cool during mild outdoor conditions the BOIL Start setting should be increased Outdoor Starting Temperature OUTDR Start The OUTDR Start ...

Page 6: ...esign __________________________________ WWSD ______________________________________ Differential Example 10 F 6 C Btu hr input 100 000 Btu hr System US GPM x 500 20 US GPM x 500 ADJUST MENU To enter the adjustment mode Press and Hold simultaneously the Item and Buttons The ADJUST element will turn on Start Interstage Delay DHW Demand Boiler Demand BOIL F ADJUST Start Interstage Delay DHW Demand B...

Page 7: ... not be connected to the control while the test is performed Using the chart below estimate the temperature measured by the sensor The sensor and thermometer readings should be close If the test meter reads a very high resistance there may be a broken wire a poor wiring connection or a defective sensor If the resistance is very low the wiring may be shorted theremaybemoistureinthesensororthesensor...

Page 8: ...or Design 60 to 32 F 51 to 0 C 10 F 12 C Boiler Minimum Off 80 to 180 F Off 27 to 82 C 140 F 60 C Differential Auto 2 to 42 F Auto 1 to 24 C Auto Interstage Delay 0 30 to 4 00 minutes 2 00 min WWSD 35 to 100 F Off 2 to 38 C Off 70 F 21 C Units F C F Do It Once Do It Right TACO INC 1160 Cranston Street Cranston RI 02920 Telephone 401 942 8000 FAX 401 942 2360 TACO Canada Ltd 6180 Ordan Drive Missis...

Reviews: