13
Parameter
Variable Name
Function
Sub Name
Valid Range
Default value
09
Auto Mode
0 = Not Active
1 = Active
0
10
Temperature
Scale
0 = °C
1 = °F
°F
11
Pipes # Main
out config
2 = 2 pipe
4 = 4 pipe
4 pipe
12
Sequence of
Operation
0 = Cooling Only
1 = Heating Only
2 = Cooling & Reheat
3 = Heating & Reheat
4 = Cooling/Heating 4 pipes
5 = Cooling /Heating 4 pipes
& Reheat
1 = Heating
Only
13
Fan Menu
0 = Low-Med-High
1 = Low-High
2 = Low-Med-High-Auto
3 = Low-High-Auto
4 = On-Auto
4 = On-Auto
14
Heat
Maximum
Setpoint
40 to 90°F
(4.5 to 32°C)
90°F (32°C)
15
Cool Minimum
Setpoint
54 to 100°F
(12 to 37.5°C)
54°F (12°C)
16
Setpoint Type
0 = Permanent
1 = Temporary
0
17
Temporary
Occ Time
0, 1, 2, 3, up to 24 hours
2 hours
18
Deadband
2, 3, 4 or 5 °F
(1 to 2.5°C)
2°F (1°C)
19
Calibration
Room Sensor
± 5°F (±2.5°C)
0°C
20
Auxiliary
Contact Config
0 = Aux Contact used for
reheat
1 = Aux NO with occupancy
2 = Aux NC with occupancy
3 = Aux NO with occupancy
& Fan On
4 = Aux NC with occupancy
& Fan On
5 = Remote control
nviAucOut
0
21
Reheat Time
Base
0 = 15 minutes
1 = 10 seconds
0
22
Fan Mode
0 = Low
1 = Med
2 = High
3 = Auto
4 = On
Depending on
Fan Menu
Selected
23
PIR Stand-By
Timer
0.5 to 24.0 Hours
0.5 Hours
Thermostat’s
common
configuration
parameters
network input
config
UNVT_fc_gen_opts
nciGenOpts
24
PIR
Unoccupied
Timer
0.0 to 24.0 Hours
0.0 Hours