background image

2

Supply
Sensor (S2)

Return
Sensor (S1)

P1

DIP 5 = Off (Linear Output Characteristic)
DIP 3 = Off (Direct Acting)
DIP 1 = On (

T Target)

Off

On

1

2

3

4

5

“00-VS”

The 00-VS adjusts the variable speed output to the P1 pump to maintain a setpoint temperature difference (

T) between the supply 

sensor and the return sensor whenever a heat demand is present.

Supply
Sensor (S2)

Return
Sensor (S1)

Condensing
Boiler

P1

DIP 5 = Off (Linear Output Characteristic)
DIP 3 = On (Reverse Acting)
DIP 1 = On (

T Target)

Off

On

1

2

3

4

5

“00-VS”

The 00-VS adjusts the variable speed output to the P1 pump to maintain a setpoint temperature difference (

T) between the supply 

sensor and the return sensor whenever a heat demand is present. This control configuration incorporates a minimum variable speed 
output percentage during operation. Refer to Minimum Variable Speed Output under the 

T Target section for selecting the available 

minimum variable speed output percentages.

Supply
Sensor 
(S1 or S2)

Cooling
Storage
Tank

P1

DIP 5 = Off (Linear Output Characteristic)
DIP 3 = On (Reverse Acting)
DIP 1 = Off (Setpoint Target)

Off

On

1

2

3

4

5

“00-VS”

The 00-VS adjusts the variable speed output to the P1 pump to maintain a setpoint temperature at the supply sensor whenever a 
heat demand is present. This application is typical of radiant cooling system. It is important to note that the 00-VS does not consider 
condensation control. Condensation prevention on surfaces must be controlled externally from the 00-VS control.

(Ts)

Ts

(Tb)

Tb = Boiler supply temperature

convectors and 10

°

F for radiant floor heating)

Ts = System supply temperature

Ts = System supply temperature (Typically 20

°

F for

Note 1

Fig. 1

Note 1

Note 2

Note 2

Note 3

Balancing

Valve

Note 3

00-VS

Injection Pump

When  the  injection  pump  is  turned  off,  there  must  be  no  heat 
transfer from the boiler loop to the system loop. In order to avoid 
this unwanted heat transfer, primary/secondary piping tech-
niques are used as shown in figure 1.
This piping arrangement requires that the injection piping be at 
least one pipe diameter smaller than the piping of the boiler and 
system  loops.  There  must  be  no  more  than  4  pipe  diameters 
between the tees in the boiler and system loops (Note 1), in 
order to prevent ghost flow when the injection pump is off and 
the system or boiler pump is on. Also, there must be at least 6 
pipe diameters of straight pipe on either side of the tees (Note 2), 
in order to prevent the momentum of water from the boiler and 
system loops from pushing flow through the injection loop. 
Finally, there should be a minimum of 1 foot drop in the injection 
loop in order to create a thermal trap (Note 3) in order to prevent 
convective heat transfer through the injection loop.

Variable Speed Injection Mixing

Variable Speed Injection Mixing uses a pump as a mixing device instead of a 2-way, 3-way or 4-way valve. The 00-VS injects hot water 
from the boiler loop into the cooler system loop. The speed of the pump is modulated in order to inject different rates of hot water into 
the cooler system return water. This allows for virtually any water temperature to be supplied to the heating system. Most boilers cannot 
operate at low temperatures, therefore the 00-VS injection pump can be modulated back in order to prevent the boiler from operating at 
cold temperatures.

Design Procedure

In order to properly size the pump, follow the design procedure below:
1)  Determine the design operating temperatures of the system loop and boiler. (Ts and Tb from figure 1.)
2) Determine the flow rate and design temperature drop (

T: Delta T) in the system loop. If one of these variables is unknown, use 

Equation 1 or 2 to determine the other variable.

3)  Compute Tb - Ts. Look up the flow rates on figure 2.
4)  The design injection flow rate for direct injection is calculated in Equation 3. If the injection flow rate is greater than 40 US GPM, a 

3-way or 4-way valve may be required.

00-VS-6

00-VS-5

00-VS-7

Summary of Contents for 00-VS

Page 1: ...ture the variable speed output is adjusted to ensure the boiler inlet temperature is above the boiler inlet minimum setpoint The 00 VS adjusts the variable speed output to the P1 pump to maintain a setpoint temperature at the supply sensor whenever a heat demand is present While the control is operating to maintain the setpoint temperature the variable speed output is also adjusted to ensure the b...

Page 2: ...unwanted heat transfer primary secondary piping tech niques are used as shown in figure 1 This piping arrangement requires that the injection piping be at least one pipe diameter smaller than the piping of the boiler and system loops There must be no more than 4 pipe diameters between the tees in the boiler and system loops Note 1 in order to prevent ghost flow when the injection pump is off and t...

Page 3: ...est signal is present at the Heat Request Ht Req terminals A heat request signal may be provided by external end switches from zone valves or ZVC SR series zone controls applying a dry contact closure or a powered 24 V ac signal across the Ht Req terminals If end switches or switching relays are not available a jumper must be installed to provide a heat request Once a heat request signal is presen...

Page 4: ...al where the first and last temperatures from the selected temperature range corresponds to 1 and 10 respectively on the RANGE dial with the temperature increasing in 5ºF increments Note Only one of the sensors S1 or S2 can be connected in this mode of operation Boiler Protection When either system sensor S1 or system sensor S2 is installed for setpoint operation and the boiler return sensor S3 is...

Page 5: ...his signal may come from zone valve end switches Taco ZVC SR series zone controls or thermostats When a thermostat is connected directly to the heat request terminals use dry contact style i e mechanical digital hard wired or digital battery operated Sensors Do not apply power to these terminals as this will damage the PC Board The wiring terminals for the sensors may be removed for ease of instal...

Page 6: ...ce In addi tion to this the actual temperature must be measured with a good quality digital thermometer First measure the temperature using the thermometer and then measure the resistance of the sensor at the 00 VS The wires from the sensor must not be connected to the PC Board while this test is performed The wiring terminals are easily removed by pulling them from the PC Board Using the chart be...

Page 7: ...s between the cartridge flange and motor 6 Make sure the replacement cartridge corresponds to the full circulator product number A complete parts list is available from your local plumbing supply wholesaler 7 Reassemble the circulator using the new gasket and bolts supplied 8 Follow the Installation procedure to start up the circulator Replacing Integral Flow Check IFC Assembly if applicable 1 Dis...

Page 8: ...replacement products and parts which are substantially similar in design and functionally equivalent to the defective product or part Taco reserves the right to make changes in details of design construc tion or arrangement of materials of its products without notification TACO OFFERS THIS WARRANTY IN LIEU OF ALL OTHER EXPRESS WARRANTIES ANY WARRANTY IMPLIED BY LAW INCLUDING WARRANTIES OF MERCHANT...

Reviews: