background image

iWorx® HPU Series

12

 

502-025, Effective: April 17, 2013 

© 2013 Taco Electronic Solutions, Inc.

TROUBLESHOOTING TIPS

This section provides remedies for common problems.

Getting Help

Components within an iWorx® controller, sensor, or power supply cannot be field repaired. If there is a problem with a unit, 
follow the steps below before contacting your local TES representative or TES technical service.

1.Make sure controllers, sensors, and power supplies are connected and communicating to desired devices.
2.Record precise hardware setup indicating the following:

Version numbers of application software.

Device and/or firmware version number.

A complete description of difficulties encountered.

Problem

Solution

Controller is not running and Status LED is not 
illuminated.

No power to controller. Verify the voltage on the controller's 
power connector (24 VAC).

How do I reset the controller?

The controller can be reset by the LCI, or you can cycle power 
to the controller. Refer to the LCI documentation for more infor-
mation on resetting the controller using the LCI.

The fan will not cycle on after the equipment 
status input alarm has been resolved

If the controller was previously in a fan fault condition, the con-
troller must be reset before proper operation can be restored.

The fan and heat/cool pilot relays will not come 
on even though the LCI indicates it is on.

Ensure that the controller and output pilot relay have been pow-
ered with 24 VAC and the output has been correctly wired to the 
coil of the pilot relay. Also ensure that the pilot relay has a 24 
VAC coil.

The 10K thermistor reading is at its maximum or 
minimum.

The input is either shorted or open.

The Heat or Cool outputs will not come on even 
though the space requires conditioned air.

Is there water flow in the system? Verify the associated CCU2 
or LHP2 controller are operating and the HPU2 is a member of 
the controller. If there is no CCU2 or LHP2 connected, then the 
Unit Enable input of the ASM2 must detect water flow (On).

Thermistor readings fluctuate rapidly, some-
times by several degrees.

The controller is not properly grounded. The controller's ground 
(GND) pin (T40) must be connected to earth ground. Also 
ensure that the controller's digital inputs are dry contacts and 
that no voltage is being applied or switched to the inputs.

How do I associate my HPU controllers with the 
LHP2?

Use the LHP2's grouping mechanism, specifically Members on 
the LHP2 HVAC Setup screen of the LCI. Only HPU controllers 
may be associated with the LHP2.

What is Save for in the Members screen and 
when do I press it?

This button stores network information into the LHP2 about the 
controllers in its group. Press this button when you have made 
any changes to the grouping.

What iWorx® controllers can be part of a 
LHP2's group?

Only HPU controllers can be part of the LHP2's group and 
demand cooling or heating from it.

Under what conditions does the HPU require a 
reset for normal operation.

There is one condition that requires a reset: - Equipment failure

Summary of Contents for iWorx HPU2

Page 1: ...internally limited to 0 04 A TS300 Series Electrical Outputs Modulated Fan HPU3 only Analog 0 10 Vdc 2K Ohm minimum load 8 bit resolution Stage 1 Stage 2 Reversing Valve Fan Dehumidification HPU3 only...

Page 2: ...lass 2 external power source not supplied to operate The controller power input requires a voltage of 24 Volts AC To calculate power source current requirements add the power consumption of all periph...

Page 3: ...onnect the equipment to a power source different from that to which the receiver is connected Consult the equipment supplier or an experienced radio TV technician for help You are cautioned that any c...

Page 4: ...iWorx HPU Series 4 502 025 Effective April 17 2013 2013 Taco Electronic Solutions Inc...

Page 5: ...iWorx HPU Series 502 025 Effective April 17 2013 5 2013 Taco Electronic Solutions Inc...

Page 6: ...be shorted Setup Instructions 1 Press Controllers from main screen 2 Select required HPU from controller list and press appropriate controller 3 Press All Settings 4 Press Thermostat 5 The Thermostat...

Page 7: ...p Stages 9 The Comp Stages menu opens a Select number of Stages of equipment 1 or 2 b Select the stage Control Band in degrees Cannot be set to 0 c Select the Stage Time in minutes Cannot be set to 0...

Page 8: ...iWorx HPU Series 8 502 025 Effective April 17 2013 2013 Taco Electronic Solutions Inc...

Page 9: ...iWorx HPU Series 502 025 Effective April 17 2013 9 2013 Taco Electronic Solutions Inc...

Page 10: ...shorted Setup Instructions 1 Press Controllers from main screen 2 Select required HPU3 from controller list and press appropriate controller 3 Press All Settings 4 Press Dehumidification 5 The Dehumid...

Page 11: ...s 1 Press Controllers from main screen 2 Select required HPU3 from controller list and press appropriate controller 3 Press All Settings 4 Press Next 3 5 Press Mod Fan Settings 6 The Mod Fan Settings...

Page 12: ...lot relay have been pow ered with 24 VAC and the output has been correctly wired to the coil of the pilot relay Also ensure that the pilot relay has a 24 VAC coil The 10K thermistor reading is at its...

Page 13: ...ormation please refer to the last page of this Document for the company s Limited Warranty Statement which is also issued with the product or available at www taco hvac com Notes Description Audience...

Page 14: ...iWorx HPU Series 14 502 025 Effective April 17 2013 2013 Taco Electronic Solutions Inc...

Page 15: ...iWorx HPU Series 502 025 Effective April 17 2013 15 2013 Taco Electronic Solutions Inc...

Page 16: ...be covered by this warranty TES products are not intended for use to support fire suppression systems life support systems critical care applications commercial aviation nuclear facilities or any othe...

Reviews: