background image

-5-

1. Location: 

The circulator can be installed on the supply or return side of the water heater or heat  

  source. See Figures 2 & 3 on pages 3 and 4 for preferred locations.

2.  Mounting Position: 

Circulator must be mounted with the motor in the horizontal position.    

  See diagrams below for acceptable motor mounting orientations.

3.  Flange Model:

 Fasten circulator to system piping. The circulator flanges incorporate a   

 

nut-grabber feature for easier installation.

CAUTION: 

Do not use flat rubber gaskets. Only use O-ring gaskets provided  

 

 

or leaks may result. Warranty will be voided.

4.  Union Model:

 Install the union tailpiece fitting set (sold separately) best suited for your  

 

  system piping. (See Union Fitting Options chart on the back cover). Install circulator by attaching  

  pump casing to each union tailpiece fitting. Tighten union nut onto circulator threading  

 

  (being careful not to overtighten) to complete the installation.

CAUTION:

 Only use union gaskets provided with union fitting sets or leaks may result.    

Warranty will be voided.

ACCEPTABLE MOTOR MOUNTING POSITIONS AND EASY CASING ROTATION

Integral Flow Check (IFC®) option — An IFC® is included in carton. If required, press IFC into the  

 

machined discharge port with plunger and O-ring facing in, until it snaps into place. Before  

 

installing, press IFC plunger to be sure it moves freely. See figures 4 & 5 above

5.  Filling the system:

 The system must be filled before operating the circulator. The bearings are   

water lubricated and should not be allowed to operate dry. It is always good practice to flush  

 

a new system of foreign matter before starting the circulator. See page 3 for recommended  

 

  air purging steps.

CAUTION

: To reduce the possibility of noise transmission, be sure to add vibration  

dampeners to piping when mounting circulator to wall or floor joists.

ATTENTION

: Pour réduire la possibilité de transmission de bruit, veillez à ajouter des  

amortisseurs de vibration à la tuyauterie lors du montage du circulateur sur des  

chevêtres de mur ou de plancher. 

WARNING:

 Risk of electric shock. To reduce the risk of electric shock, be certain that it is 

connected only to a properly grounded, grounding-type receptacle. Follow all local elec-

trical and plumbing codes.

AVERTISSEMENT:

 Risque de choc électrique. Pour réduire le risque de choc électrique, 

veillez à ce qu’elle soit raccordée uniquement àun réceptacle de type mise à la terre  

proprement mis à la terre. Respectez tous les codes de plomberie et électriques locaux.

Always install with motor in 

horizontal orientation. Position 

electrical junction box at 9 o’clock 

for best viewing orientation. Pump 

casing may be rotated to change 

flow direction. Locate the arrow 

on the casing body to determine 

flow direction.

To rotate the pump casing, remove the 4 motor screws. 

When rotating 

pump casing position, DO NOT detach motor housing from the 

casing. 

Damage to the casing O-ring and leakage may result. Simply spin 

casing to the proper flow direction desired as shown in Figure 4 and 

Figure 5. Reattach the 4 screws (1⁄8” allens wrench required). Be sure 

motor is positioned correctly and is seated evenly to prevent leakage or 

damage to O-ring. Tighten motor screws evenly to 

25-38

 in-lbs torque.

Spin 

casing 

to 

change 

flow 

direction.

Figure 4

Figure 5

Figure 6

Spin casing 

to change 

flow direction.

Do not detach motor frame 

from pump casing. Simply 

spin casing to the proper

flow direction

Summary of Contents for 007e Series

Page 1: ...e or closed loop hydronic heating systems Not suitable for chilled water systems Taco circulator pumps are for indoor use only employer uniquement a l interieur Acceptable for use with water or maximum of 50 water glycol solution FEATURES ECM performance equivalent to Taco s legendary 007 circulator Use with Taco SmartPlug Instant Hot Water Control for hot water when you need it Multi color LED sh...

Page 2: ... additives to systems using TACO equipment voids the warranty Consult factory for fluid compatibility ATTENTION L ajout de liquides à base de pétrole ou de certains additifs chimiques à des systèmes utilisant un équipement TACO annule la garantie Consultez le fabricant pour con naître la compatibilité de liquides CAUTION Installations at elevations over 5000 feet must have higher fill pressure of ...

Page 3: ...n system Open all isolation valves Once system is filled close the fixture at the highest point in the system Close isolation valve on pump discharge Option No 1 location Open drain valve on pump discharge until all remaining air has been purged Close drain valve Operate pump until all remaining air is purged from bearing chamber 2 3 4 5 6 7 ...

Page 4: ...Open FF valve Open V2 PV4 to purge last zone First Zone 3 Close FF Valve Close V2 PV4 Repeat steps 1 to 6 for each additional zone purge zone 1 last Open V1 when all zones are purged Adjust system to desired operating fill pressure if required 2 3 4 5 6 7 8 9 V1 V2 V3 Shut off Isolation Valve P Taco circulator with IFC installed FF Fast Fill Boiler Feed Valve PV4 Purge Valve ...

Page 5: ... the circulator See page 3 for recommended air purging steps CAUTION To reduce the possibility of noise transmission be sure to add vibration dampeners to piping when mounting circulator to wall or floor joists ATTENTION Pour réduire la possibilité de transmission de bruit veillez à ajouter des amortisseurs de vibration à la tuyauterie lors du montage du circulateur sur des chevêtres de mur ou de ...

Page 6: ...e CAUTION Never run the circulator dry or permanent damage may result ATTENTION Ne laissez jamais le circulateur tourner à sec des dommages permanents peuvent en résulter CAUTION Do not attempt to remove LED panel from circulator Serious damage to circulator electronics may result ATTENTION N essayez pas de retirer le panneau de LED du circulateur Des dommages sérieux à l électronique du circulate...

Page 7: ... 7 Orange LED Green LED Proportional Pressure Mode 007e Performance Curves Normal Mode Green Mode 007e Performance Curves ...

Page 8: ...k for impeller rotation 7 If the circulator still doesn t run it will need to be replaced FAULTS CONTROL PANEL CAUSES REMEDIES The circulator is noisy LED on Suction pressure is insufficient cavitation Increase the system suction pressure within the permissible range LED on Presence of foreign bodies in the impeller Disassemble the motor and clean the impeller Loud noises of water circulation Flas...

Page 9: ...SOLDSEPARATELY Part Description UFS 050S 1 2 Sweat tailpiece set UFS 050T 1 2 NPT tailpiece set UFS 050P 1 2 Press tailpiece set UFS 075S 3 4 Sweat tailpiece set UFS 075T 3 4 NPT tailpiece set UFS 075P 3 4 Press tailpiece set Lead FreeShut Off FLANGE SOLDSEPARATELY Part Description SFL 050T 1 2 NPT SFL 050S 1 2 Sweat SFL 075T 3 4 NPT SFL 075S 3 4 Sweat SFL 100T 1 NPT SFL 100S 1 Sweat SFL 125T 1 1 ...

Page 10: ... 10 NOTES ...

Page 11: ... 11 NOTES ...

Page 12: ...consequential damages so these limitations or exclusions may not apply to you LIMITED WARRANTY STATEMENT Taco Inc will repair or replace without charge at the company s option any Taco product which is proven defective under normal use within three 3 years from the date code In order to obtain service under this warranty it is the responsibility of the purchaser to promptly notify the local Taco s...

Reviews: