43
Special Condition Description
INDICATION CONTENT
DESCRIPTION
Zero Speed
Stopping
When F_11 = 0, F_7= 0 and frequency setting < 1 Hz
When F_11 = 1, F_7<(F_6/100), and frequency setting
<(F_6/100)
Fail to start
directly
1. If the inverter is set to external operation (F_10 = 1) and
direct start is disabled (F_28 =1), the inverter cannot be
started and will flash SP1 when operation switch turned to
ON after applying power (see descriptions of F_28).
2. Direct start is possible when F_28 = 0.
Keypad
emergency stop
The inverter setup to external operation (F_10=1). If the STOP
key in the keypad is pressed at the middle of operation, the
inverter stops according the setting in F_14 and flash SP2 after
stop. The RUN switch must be turned OFF than ON to restart
the machine.
External
emergency stop
When the external emergency stop signal is activated through
the multi-function input terminal, the inverter decelerates and
stops. Inverter flashes E.S. after stops. (Refer to instruction for
F_19 for detail).
External BASE
BLOCK
When the external BASE BLOCK signal is activated through the
multifunction terminal, the inverter stop output immediately and
flash b.b. for indication. (Refer to instruction for F_19 for detail)
Keypad Operation Error Instruction
INDICATION CONTENT POSSIBLE
CAUSE
COUNTERMEASURE
Motor direction
locked
1. Attempt to reverse direction
when F_22 = 1
2. Attempt to set F_22 to 1 when
F_04 = 1
1. Adjust F_22 to 0
2. Adjust F_04 to 0
Keypad
operation error
1. Press
▲
or
▼
keys when
F_11=1 or under sp1 operation
2. Attempt to modify F_29
3.Attempt to modify parameter that
is not allowed to be modified
during operation (refer to
parameter list)
1. Use
▲
or
▼
keys to
adjust frequency setting
only after F_11=0
2. Do not modify F_29
3. Modify in stop mode
Parameter
setting error
1. F_6
≦
F_7
1. F_6 > F_7
SP0
LOC
Er1
Er2
E.S.
b.b.
SP2
SP1