![t.a.c. Xenta OP Handbook Download Page 29](http://html1.mh-extra.com/html/t-a-c/xenta-op/xenta-op_handbook_3091278029.webp)
TAC AB, 2001-08-08
0-004-7506-4 (EN), 29 (36)
TAC Xenta OP Handbook
4 Dialogs with TAC Xenta 300 and 401
4.6
Edit access code
To change the code that gives the operator access to the medium or
high level items, the access level code for the level to be changed must
first be entered as described above. Then go to the Edit Access Code
screen:
A2: EDIT ACCESS CODE
EDIT CODE: 0000
Change code for
the active level (no.)
Use
to move the cursor between the digits and use
+
and
–
to change their value. When finished, press
and leave the
menu with
. As the access code is changed only the standard
(low level) items will be shown. To show the medium or high level
menu items the new access code has to be entered as described in the
previous example.
After the download of an application from TAC Menta, the access
code
will revert
to the default value.
4.7
Overriding inputs/outputs
For access code
high
, it is possible to override the input and output
values in the Status displays of the OP.
For example, to override a digital output you must indicate “manual
override” in the field just in front of the displayed value:
A2: Fan status
SF_out _0
With the cursor in the position just to the left of the 0 value, use
+
or
–
twice
to toggle up the manual override indicator (
->
).
Press
to confirm and to move the cursor to the value itself. It is
now possible to change the value, a value that will override the value
set by the controller.
The override indicator will remain visible (for all access levels) until
it is reset to normal, automatic mode.
Network Variables (please refer to the TAC Menta User’s manual)
can also be overridden in this way.
Summary of Contents for Xenta OP
Page 1: ...TAC Xenta OP Handbook 0 004 7506 4 EN 2001 08 08 AH02 West _STATUS TEMPERATURES ALARMS...
Page 2: ......
Page 32: ...32 36 0 004 7506 4 EN TAC AB 2001 08 08 TAC Xenta OP Handbook 5 Technical data Blank page...
Page 34: ...34 36 0 004 7506 4 EN TAC AB 2001 08 08 TAC Xenta OP Handbook Index Blank page...
Page 35: ......