SYX661-CSC Commissioning Guide 

 

V1.1 10/2020 

Page 9 of 17 

3

 

Equipment Selection and location 

3.1 Heating Application Example (CSC-V) - Valve Control Only 

 

 

 

 

 

 
3.2 Heating Application Example (CSC-V-T)- Pump and Valve Control 

 

  

 

3.2 Access and Controller Configuration  

To Set-up the controller, the user must be logged into the SYX661-CSC at level 2.  

To access the Logon Screen on the controller please Press and Hold the ESC button for 5 Seconds. 

Select User 2 

The passcode for Set-up level is 0112 

Turn and Press the Wheel to select the above code 

Once you have 0112 on the Controller press the Select Button to enter it 

 

To access the Logon Screen using the browser or the TPC Touchscreen select the Logon Button in the bottom corner 
and follow the same instructions as above but using the keys on the screen. Press enter on the screen to enter the 
value. 

Once at this User Level the Set-Up Menu options are available to tune the controller to the application you have. 

Each menu shown on the controller interface (shown below) has application Set-Up features inside.  

The  controller  offers  a  menu  structure  and  the  navigation  can  be  made  using  the  controller  interface  or  the  web 

Room Sensor (Optional)

 

Outside Sensor (North Wall)

 

Outside Sensor (North Wall)

 

Summary of Contents for SYX-CSC-V

Page 1: ...SYX661 CSC Commissioning Guide V1 1 10 2020 Page 1 of 17...

Page 2: ...troller Configuration 9 6 1 SYX661 CSC V T 11 7 Controller Settings in detail 11 7 1 Outside High Limit 11 7 2 Frost Protection SYX661 CSC V T Only 11 7 3 Pump Overrun 11 7 4 Valve Exercise 12 7 5 Pum...

Page 3: ...or if the flow high limit alarm has been triggered 5 C above Flow Max setting for 30 seconds The info button provides direct access to visual indication of all input and output status The Malfunction...

Page 4: ...well as those from the VDE Association for Electrical Electronic Information Technologies If the device is used in other countries it is the responsibility of the system installer or operator to compl...

Page 5: ...Influence Space Frost protection 35 30 Pin 8 Day Extend CSC V T Close the contact to put the controller into Day Mode 27 28 Pin 9 Night Reduction Open to put the controller into Night Setback Mode Th...

Page 6: ...on Details 3 4 Pin 11 VT Valve Open Actuator open signal VFC 230V or 24v reversing actuator supply to be provided 5 6 Pin 12 VT Valve Close Actuator close signal VFC 230V or 24v reversing actuator sup...

Page 7: ...s View historic information Time Schedule and Holiday Planning Configuration of all the controller options Remote overrides and time extensions Observe Live Controller Operation IP 192 168 1 99 SM 255...

Page 8: ...de control of simple Variable Temperature circuits On start up the settings have been pre set to give sensible values suitable for a Radiator VT Heating System the settings can be adapted to suit othe...

Page 9: ...the above code Once you have 0112 on the Controller press the Select Button to enter it To access the Logon Screen using the browser or the TPC Touchscreen select the Logon Button in the bottom corne...

Page 10: ...rs two different browser options as shown below with and without mo after the IP address of the controller and either can be used Above example 192 168 1 99 mo Above example using basic browser on 192...

Page 11: ...de High Limit The Outside High feature will disable the heating if the Outside Air Temperature goes above this Set point for 10 minutes The Outside Air Temperature will need be one degree below the Ou...

Page 12: ...time extend period when the input closes The external timer input is not interlocked with the time schedule and acts directly 7 7 Summer Winter Time Change and Leap Years This is fully automated Leap...

Page 13: ...io 3 0 1 20 Influence on the Heating Flow Set point based on 1 C change in Outside air temperature Flow Minimum 25 C 0 C 150 C Minimum value of compensated flow temperature during compensation Flow Ma...

Page 14: ...ack on 1 C below this value Outside Frost Set point 3 C 10 C 10 C If outside temperature falls below the Outside Frost limit the valve will be opened and the heating pump will switch on Pump Run On 0...

Page 15: ...to Enter it Level 0 0000 Level 1 1111 Level 2 0112 Level 3 Reserved 8 3 Factory Defaults Do not try to reset the controller There is no factory default reset feature Once parameters have been changed...

Page 16: ...ated from a power supply to avoid unwanted alarms Alarms can be acknowledged by pressing the lower left button on the controller facia Old Alarms that are no longer active can be cleared by pressing a...

Page 17: ...User 1 1111 User 2 is 0112 User 3 is for special access purposes only Q I want to change the controller IP address how can this be done A Contact SyxthSense and we will provide assistance on this Q Do...

Page 18: ...ioning Guide V1 1 10 2020 Page 18 of 17 SyxthSense Ltd 3 Topsham Units Dart Business Park Topsham Exeter EX3 0QH United Kingdom Tel 0844 840 3100 Fax 0844 840 3200 Email info syxthsense com Internet w...