SYX661-CSC Commissioning Guide 

 

V1.1 10/2020 

Page 4 of 17 

1.1

 

Important Information Regarding Product Safety 

 
  Safety Instructions 

This document contains information on installing and commissioning the product "SYX66x". Each person who carries 
out  work  on  this  product  must  have  read  and  understood  this  document.  If  you  have  any  questions  that  are  not 
resolved by this document, you can obtain further information from the supplier. 

 

If the product is not used in accordance with this document, the protection provided will be impaired. 

Applicable  regulations  must  be  observed  when  installing  and  using  the  device.  Within  the  EU,  these  include 
regulations regarding occupational safety and accident prevention as well as those from the 

VDE (Association for Electrical, Electronic & Information Technologies). If the device is used in other countries, it is 
the responsibility of the system installer or operator to comply with local regulations. 

Mounting,  installation  and  commissioning  work  on  the  devices  may  only  be  carried  out  by  qualified  technicians. 
Qualified technicians are persons who are familiar with the described product and who can assess given tasks and 
identify possible dangers due to technical training, knowledge and experience as well as knowledge of the appropriate 
regulations. 

 

 

 
 

1.2

 

Notes on Disposal 

For disposal, the product is considered waste from electrical and electronic equipment (electronic waste) and must 
not  be  disposed  of  as  household  waste.  Special  treatment  for  specific  components  may  be  legally  binding  or 
ecologically sensible. The local and currently applicable legislation must be observed.

 

 

Summary of Contents for SYX-CSC-V

Page 1: ...SYX661 CSC Commissioning Guide V1 1 10 2020 Page 1 of 17...

Page 2: ...troller Configuration 9 6 1 SYX661 CSC V T 11 7 Controller Settings in detail 11 7 1 Outside High Limit 11 7 2 Frost Protection SYX661 CSC V T Only 11 7 3 Pump Overrun 11 7 4 Valve Exercise 12 7 5 Pum...

Page 3: ...or if the flow high limit alarm has been triggered 5 C above Flow Max setting for 30 seconds The info button provides direct access to visual indication of all input and output status The Malfunction...

Page 4: ...well as those from the VDE Association for Electrical Electronic Information Technologies If the device is used in other countries it is the responsibility of the system installer or operator to compl...

Page 5: ...Influence Space Frost protection 35 30 Pin 8 Day Extend CSC V T Close the contact to put the controller into Day Mode 27 28 Pin 9 Night Reduction Open to put the controller into Night Setback Mode Th...

Page 6: ...on Details 3 4 Pin 11 VT Valve Open Actuator open signal VFC 230V or 24v reversing actuator supply to be provided 5 6 Pin 12 VT Valve Close Actuator close signal VFC 230V or 24v reversing actuator sup...

Page 7: ...s View historic information Time Schedule and Holiday Planning Configuration of all the controller options Remote overrides and time extensions Observe Live Controller Operation IP 192 168 1 99 SM 255...

Page 8: ...de control of simple Variable Temperature circuits On start up the settings have been pre set to give sensible values suitable for a Radiator VT Heating System the settings can be adapted to suit othe...

Page 9: ...the above code Once you have 0112 on the Controller press the Select Button to enter it To access the Logon Screen using the browser or the TPC Touchscreen select the Logon Button in the bottom corne...

Page 10: ...rs two different browser options as shown below with and without mo after the IP address of the controller and either can be used Above example 192 168 1 99 mo Above example using basic browser on 192...

Page 11: ...de High Limit The Outside High feature will disable the heating if the Outside Air Temperature goes above this Set point for 10 minutes The Outside Air Temperature will need be one degree below the Ou...

Page 12: ...time extend period when the input closes The external timer input is not interlocked with the time schedule and acts directly 7 7 Summer Winter Time Change and Leap Years This is fully automated Leap...

Page 13: ...io 3 0 1 20 Influence on the Heating Flow Set point based on 1 C change in Outside air temperature Flow Minimum 25 C 0 C 150 C Minimum value of compensated flow temperature during compensation Flow Ma...

Page 14: ...ack on 1 C below this value Outside Frost Set point 3 C 10 C 10 C If outside temperature falls below the Outside Frost limit the valve will be opened and the heating pump will switch on Pump Run On 0...

Page 15: ...to Enter it Level 0 0000 Level 1 1111 Level 2 0112 Level 3 Reserved 8 3 Factory Defaults Do not try to reset the controller There is no factory default reset feature Once parameters have been changed...

Page 16: ...ated from a power supply to avoid unwanted alarms Alarms can be acknowledged by pressing the lower left button on the controller facia Old Alarms that are no longer active can be cleared by pressing a...

Page 17: ...User 1 1111 User 2 is 0112 User 3 is for special access purposes only Q I want to change the controller IP address how can this be done A Contact SyxthSense and we will provide assistance on this Q Do...

Page 18: ...ioning Guide V1 1 10 2020 Page 18 of 17 SyxthSense Ltd 3 Topsham Units Dart Business Park Topsham Exeter EX3 0QH United Kingdom Tel 0844 840 3100 Fax 0844 840 3200 Email info syxthsense com Internet w...