background image

SYX661-CSC Commissioning Guide 

 

V1.1 10/2020 

Page 16 of 17 

9.

 

Overrides 

The controller allows the control mode to be manually set, this can be achieved by using the override menu. Chose 
Switch and select the mode you require. Night/Boost/Off/Auto the CSC-V-T version offers Continuous Mode also 
for permanent Day mode. 

The controller allows the valve position to be manually set, the can this can be achieved by using the override 
menu. Chose Switch and select the option you require.  Open/Close/Hold/Auto 

The Hand light will illuminate until the controller is returned to the Auto Mode. 

The external overrides (Volt free contacts) work to override the controller also. If Night and Boost are set at the 
same time by external or software override then Night mode will have priority. 

 

10.

 

Alarms and Management 

10.1

 

Flow High Limit 

If the flow sensor sees a temperature 5 

C higher than the flow max setting for more then 30 seconds then the flow 

high temp alarm will be triggered and the heating will be shut down until the flow temperature has cooled 5

lower than the flow max setting. 

10.2

 

Sensor Alarms  

All Sensors are monitored for correct connection. Messages will be populated based on the time and date of 
disconnection. It is essential that wiring of sensors is made when the controller is isolated from a power supply to 
avoid unwanted alarms.  

Alarms can be acknowledged by pressing the lower left button on the controller facia. 

Old Alarms that are no longer active can be cleared by pressing and holding the lower left button for over 5 
seconds. 

 

11.

 

Maintenance and Warranty 

The controller itself requires no maintenance. The controller is covered by a 12 month warranty. 

12.

 

 FAQ 

Q. Will the controller compensate the Boilers? 

A. No. To compensate boilers please use the SYX661 Optimiser Compensator. 

Q. Will the SYX66x controller provide 24vAC for my actuator? 

A.  No.  You  will  require  an  external  Power  Supply.  An  isolating  Transformer  is  preferred.  Please  see  the  wiring 
examples provided with the controller and on the data sheet. 

Q. Can I re-use the existing wiring? 

A. Yes. If the wiring worked on the previous controller then there is no real reason why they cannot be re-used. If the 
wiring causes issues with the controller it has probably caused issues with the old device as well. If replacing sensor 
wiring then use Screened Twisted Pair cable from the sensor all the way through the panel onto the controller 
terminal.  

Q. The sensors are not reading as I would expect. 

If the sensors are going up and down please observe screening cable recommendations and grounding of cable 
screens. Also check that the correct GND connections have been used for all inputs and outputs. If the sensors are 
reading a little high or a little low then use the sensor calibration feature in the Connections Menu. 

Summary of Contents for SYX-CSC-V

Page 1: ...SYX661 CSC Commissioning Guide V1 1 10 2020 Page 1 of 17...

Page 2: ...troller Configuration 9 6 1 SYX661 CSC V T 11 7 Controller Settings in detail 11 7 1 Outside High Limit 11 7 2 Frost Protection SYX661 CSC V T Only 11 7 3 Pump Overrun 11 7 4 Valve Exercise 12 7 5 Pum...

Page 3: ...or if the flow high limit alarm has been triggered 5 C above Flow Max setting for 30 seconds The info button provides direct access to visual indication of all input and output status The Malfunction...

Page 4: ...well as those from the VDE Association for Electrical Electronic Information Technologies If the device is used in other countries it is the responsibility of the system installer or operator to compl...

Page 5: ...Influence Space Frost protection 35 30 Pin 8 Day Extend CSC V T Close the contact to put the controller into Day Mode 27 28 Pin 9 Night Reduction Open to put the controller into Night Setback Mode Th...

Page 6: ...on Details 3 4 Pin 11 VT Valve Open Actuator open signal VFC 230V or 24v reversing actuator supply to be provided 5 6 Pin 12 VT Valve Close Actuator close signal VFC 230V or 24v reversing actuator sup...

Page 7: ...s View historic information Time Schedule and Holiday Planning Configuration of all the controller options Remote overrides and time extensions Observe Live Controller Operation IP 192 168 1 99 SM 255...

Page 8: ...de control of simple Variable Temperature circuits On start up the settings have been pre set to give sensible values suitable for a Radiator VT Heating System the settings can be adapted to suit othe...

Page 9: ...the above code Once you have 0112 on the Controller press the Select Button to enter it To access the Logon Screen using the browser or the TPC Touchscreen select the Logon Button in the bottom corne...

Page 10: ...rs two different browser options as shown below with and without mo after the IP address of the controller and either can be used Above example 192 168 1 99 mo Above example using basic browser on 192...

Page 11: ...de High Limit The Outside High feature will disable the heating if the Outside Air Temperature goes above this Set point for 10 minutes The Outside Air Temperature will need be one degree below the Ou...

Page 12: ...time extend period when the input closes The external timer input is not interlocked with the time schedule and acts directly 7 7 Summer Winter Time Change and Leap Years This is fully automated Leap...

Page 13: ...io 3 0 1 20 Influence on the Heating Flow Set point based on 1 C change in Outside air temperature Flow Minimum 25 C 0 C 150 C Minimum value of compensated flow temperature during compensation Flow Ma...

Page 14: ...ack on 1 C below this value Outside Frost Set point 3 C 10 C 10 C If outside temperature falls below the Outside Frost limit the valve will be opened and the heating pump will switch on Pump Run On 0...

Page 15: ...to Enter it Level 0 0000 Level 1 1111 Level 2 0112 Level 3 Reserved 8 3 Factory Defaults Do not try to reset the controller There is no factory default reset feature Once parameters have been changed...

Page 16: ...ated from a power supply to avoid unwanted alarms Alarms can be acknowledged by pressing the lower left button on the controller facia Old Alarms that are no longer active can be cleared by pressing a...

Page 17: ...User 1 1111 User 2 is 0112 User 3 is for special access purposes only Q I want to change the controller IP address how can this be done A Contact SyxthSense and we will provide assistance on this Q Do...

Page 18: ...ioning Guide V1 1 10 2020 Page 18 of 17 SyxthSense Ltd 3 Topsham Units Dart Business Park Topsham Exeter EX3 0QH United Kingdom Tel 0844 840 3100 Fax 0844 840 3200 Email info syxthsense com Internet w...

Reviews: