SyxthSense Ltd
Copyright © 2009 SyxthSense Ltd. All rights reserved - 03/2009
PS
SN1.125
- 3/5
Online store:
www.syxthsense.com
Enquiries: T:
0870 20 80 100
F:
0870 20 80 200
RY-FL Wiring
The diagram below illustrates the wiring details for the RY-FL device. Each RY-FL can be configured
to receive 2 input signals and control two output signals. The selection / configuration is done using
FLSER (ver 2.2 or later) service tool.
An example configuration (configurable via FLSER ver 2.2 or later):-
Input 1:Used as AI1 0..10Vdc to measure CO2 content
Input 2:Used as DI2 signal to monitor the window contacts
Output 1: Used as Relay 1 to drive the window open.
Output 2: Used as AO2 0..10Vdc control signal to drive a damper actuator.
NOTE:
Both inputs and outputs are individually configurable for the required operation. Output
configuration is done automatically via Modbus messaging.
RY-FL Addressing
Each wireless I/O-module, transmitter, repeater and F LTA control module/receiver (ver. 2.2 or later)
needs to have unique address. Wireless transmitter address consists of two parts; SID (Sensor ID)
and MID (Master ID). The I/O-module address is configured using FLSER service tool. MID is the
address of FLTA control module/receiver. Typically MID is set to one in a single FLTA network.
Example (single network, two devices):
Device 1: RY-FL IO-Module Address: SID (RYFL ID) = 1, MID = 1
Device 2: TEU-FL Address: SID = 2, MID =1
Master 1: FLTA Address: MID = 1
RY-FL and TEU-FL have MID address 1. This mens that they are transmitting
measurements/receiving output commands to FLTA that has been addressed with the same MID.
Example (two networks, two devices):
Device 1: RY-FL Address: SID (RYFL ID) = 1, MID =1
Device 2: RY-FL Address: SID (RYFL ID) = 1, MID =2
Master 1: FLTA Address: MID = 1
Master 2: FLTA Address: MID = 2
Device 1 transmits the measurements/receives commands to/from Master 1 (FLTA), and Device 2
transmits the measurements/receives commands to/from to Master 2. Although the both devices have
the same SID this will not cause problems as MID is different.
RF
ERROR
OK
CHANGE MID/SID
(SETTING ADDRESS)
RELAY 1 RELAY 2
NC NO C NC NO C
1 2 3 4 5 6 7 8
9 10
22 23 24 25
TRANSFORMER
RELA
Y 1
RELA
Y 2
RYFL
11 12 13 14 15 16
17 18
230VAC
N L
AO1
GND
24V
AC
AO2
GND
24V
AC
A1
B1
A2
B2
AI1 / DI1
AI2 / DI2
GND
GND
VALVE1 VALVE2
30 31
24VAC
(Option)
G0 G