background image

SyxthSense Ltd

Copyright © 2009 SyxthSense Ltd. All rights reserved - 03/2009 

PS 

SN1.125

 - 3/5

Online store: 

www.syxthsense.com

Enquiries: T: 

0870 20 80 100   

F:

 0870 20 80 200

RY-FL Wiring

The diagram below illustrates the wiring details for the RY-FL device. Each RY-FL can be configured 
to receive 2 input signals and control two output signals. The selection / configuration is done using 
FLSER (ver 2.2 or later) service tool.

An example configuration (configurable via FLSER ver 2.2 or later):-

Input 1:Used as AI1 0..10Vdc to measure CO2 content

Input 2:Used as DI2 signal to monitor the window contacts

Output 1: Used as Relay 1 to drive the window open.

Output 2: Used as AO2 0..10Vdc control signal to drive a damper actuator.

NOTE:

 Both inputs and outputs are individually configurable for the required operation. Output 

configuration is done automatically via Modbus messaging.

RY-FL Addressing

Each wireless I/O-module, transmitter, repeater and F LTA control module/receiver (ver. 2.2 or later) 
needs to have unique address. Wireless transmitter address consists of two parts; SID (Sensor ID) 
and MID (Master ID). The I/O-module address is configured using FLSER service tool. MID is the 
address of FLTA control module/receiver. Typically MID is set to one in a single FLTA network.

Example (single network, two devices):

Device 1: RY-FL IO-Module Address: SID (RYFL ID) = 1, MID = 1

Device 2: TEU-FL Address: SID = 2, MID =1

Master 1: FLTA Address: MID = 1

RY-FL and  TEU-FL have MID address 1.  This mens that they are transmitting 
measurements/receiving output commands to FLTA that has been addressed with the same MID.

Example (two networks, two devices):

Device 1: RY-FL Address: SID (RYFL ID) = 1, MID =1

Device 2: RY-FL Address: SID (RYFL ID) = 1, MID =2

Master 1:  FLTA Address: MID = 1

Master 2:  FLTA Address: MID = 2

Device 1 transmits the measurements/receives commands to/from Master 1 (FLTA), and Device 2 
transmits the measurements/receives commands to/from to Master 2. Although the both devices have 
the same SID this will not cause problems as MID is different.

RF

ERROR

OK

CHANGE MID/SID

(SETTING ADDRESS)

RELAY 1 RELAY 2

NC NO C NC NO C

1 2 3 4 5 6 7 8

9 10

22 23 24 25

TRANSFORMER

RELA

Y 1

RELA

Y 2

RYFL

11 12 13 14 15 16

17 18

230VAC

N L

AO1

GND

24V

AC

AO2

GND

24V

AC

A1

B1

A2

B2

AI1 / DI1

AI2 / DI2

GND

GND

VALVE1 VALVE2

30 31

24VAC 

(Option)

G0 G