background image

 

 

SyxthSense Ltd 

 

 
Online Store: 

www.syxthsense.com

 

Copyright 

©

 2004  SyxthSense Ltd – 07/2004 

Enquiries: T: 

0870 20 80 100

   F: 

0870 20 80 200

 PS 

TH6.21

 – 3/6 

 

 

 

 

 

 
 
 

 

Operation 

The thermostat can control either heating or cooling systems: the selection is made by setting an 
internal jumper JP3 (Fig. 5).  
 
In ‘heating’ mode the thermostat turns on the relevant channel output relay in the receiving unit when 
the room temperature is lower than the value set with the knob (3) (set-point temperature). When 
temperature rises over the set value the relay will be turned off. This action will be performed with an 
hysteresis of 0.3°C. The hysteresis is a fixed parameter and cannot be changed.  
 
In ‘cooling’ mode the operation logic is inverted, when temperature rises over the set value the relay 
is turned on, the relay output is meant to activate a cooling system. This action will also be 
performed with an hysteresis of 0.3°C. In both modes a night reduction of 3°C is available: this option 
can be activated through selector (1) by setting it in ‘Program’ position (i. e. the upper position). This 
function makes the thermostat operates with both the ‘comfort’ and a ‘reduced’ set-point, in order to 
get energy saving, for example during the night. In ‘heating’ mode the reduced set-point corresponds 
to the comfort set-point minus 3°C. In ‘cooling’ mode the reduced set-point corresponds to the 
comfort set-point plus 3°C.  
 
When in ‘Program’ position the thermostat sends to the receiver an additional signal which lets the 
receiver drive the relay output in a reduced way. This signal is called ‘reduced signal’ while the 
normal signal is called ‘comfort signal’. The receiving unit can then use either the signals to drive the 
relevant output.  
 
A special input (clock input) at the receiving side makes the output be controlled from the comfort or 
the reduced signal. This ability was meant to easily get a reduction during the desired hours by 
connecting a clock switch to the receiver. 
 
If there is no clock connected to the receiver, the ‘Program’ position in the thermostat will operate 
with the reduced set-point at any time. For more information see the receiver documentation. 
 
Setting selector (1) in the Comfort (i.e. the central) position will make the thermostat regulate always 
at the comfort set-point without any reduction. The Off position of the selector will always keep the 
relevant relay output in the Off state. Note that even in the Off mode the thermostat still transmits to 
the receiver signals, which will be always Off signals. This is performed to distinguish from normal 
turned off operation and the eventuality of faults on the transmitter.  
 
The thermostat is supplied with two AAA 1.5V= alkaline batteries and the red led (2) informs when 
the batteries are discharged and must be replaced. In normal operation the led is always off; on the 
other hand when it indicates the low battery state it flashes once every about 20 seconds. In order to 
grant a reasonable battery life the thermostat waits, between two consecutive transmissions, an 
amount of time that can be set in 3 or 10 minutes by moving an internal jumper JP2 (see Fig. 5). The 
3 minutes option is selected by removing JP2: this option should be chosen only with fast 
heating/cooling systems. With common heating systems like floor heating systems, the 10 minutes 
interval option provides a good accuracy and comfort.

System Start-Up 

Before installing the thermostat in the desired position, is necessary to test if the receiver unit 
correctly receives its radio signals. To do this the thermostat must be turned on in a ‘Test’ mode. 
The operation is described in the following.  
 
Open the thermostat box according to the instruction in the “Mechanical description” section. Set the 
appropriate address in the dip switch (10) visible in Fig. 5. The address can be chosen randomly but 
taking into account that several thermostats installed in the close area must operate with different 
addresses, to avoid data collision and malfunction. 
 
See also appendix A for more information.  
 
Insert the batteries, carefully respecting the polarity and do not use old, used, or non alkaline 
batteries. When inserting the batteries for the first time the red LED (2) turns immediately on for 
about 2 seconds. This displays the correct insertion of the batteries and the correct operation of the 
thermostat (this can also be obtained at any time by pressing for a while the reset button (12) visible 
in Fig. 5).  
 
In the thermostat, move the selector (1) to the OFF position and just press the ’reset’ (12) button. 
Now the thermostat is operating in ‘Test’ mode and this state is also displayed by the LED (2) which 
flashes every 3 seconds.  
 
During the test operation it is important not to move the selector (1), from the Off position, if it is 
moved the test mode finishes. The test mode also ends automatically after about 25 minutes.  
 
 

Reviews: