Systems With Intelligence DVS500 Installation Manual Download Page 10

IN

ST

AL

LA

TION

DVS500 Installation Guide - V1.0 

10

             www.SystemsWithIntelligence.com 

                                                                                   [email protected]   

© 2017 Systems With Intelligence.  All rights reserved.

4  Failsafe Relay

The failsafe relay is a digital output contact that can be used to communicate an alarm to another system

(e.g. remote terminal unit) if the server stops working. The failsafe relay is in open state (normally open)

when the server is powered down, and it is latched by the system when the server is powered up. An open 

state will indicate that the server has no power or that something is wrong with the software running in the 

server.

DVS500 OVERALL DIMENSION

Summary of Contents for DVS500

Page 1: ...hIntelligence com 2018 Systems With Intelligence All rights reserved DVS500 INSTALLATION GUIDE Version 1 0 SUBSTATION HARDENED DIGITAL VIDEO SERVER Note Please read this manual thoroughly before opera...

Page 2: ...of Systems With Intelligence Inc Disclaimer of Liability We have checked the contents of this manual against the hardware and software described However deviations from the description cannot be comp...

Page 3: ...he interference on his own expense CAUTION This product contains a laser system and is classified as a CLASS 1 LASER PRODUCT CAUTION Use of controls or adjustments or performance of procedures other t...

Page 4: ...m 5 1 2 Technical Specifications Overview 6 2 Dimensions 7 3 Power Supply 8 3 1 Power Supply Wiring 9 3 2 Dual Redundant Power Supply 9 4 Failsafe Relay 10 5 IP Camera Input 11 6 Serial Interface 12 6...

Page 5: ...x USB 2 0 Ports Digital Inputs 4 x Digital Inputs Digital Outputs 4 x Digital Outputs Mounting DIN rail mounts Substation Hardened IEC 61850 3 IEEE 1613 C37 90 400 C to 750 C Future option available s...

Page 6: ...es supported ONVIF IP Camera Support CPU Atom E3845 1 91GHz RAM 4GB DDR3L Power 30W Max Video Output 1 HDMI interface for computer monitor USB 2 USB 2 0 Ports Storage Up to 1TB LAN Interface Included...

Page 7: ...ystemsWithIntelligence com support SystemsWithIntelligence com 2017 Systems With Intelligence All rights reserved 7 INSTALLATION 2 Dimensions Note Units in Imperial Metric 3 72 in 94 5 mm 6 34 in 161...

Page 8: ...SUPPLY TYPE INPUT RANGE INTERNAL FUSE RATING POWER CONSUMPTION MIN MAX TYPICAL WORST CASE 24 48 VDC 20 VDC 60 VDC 5A T 15 W 20 W 25 W 30 W TERMINAL NUMBER DESCRIPTION USAGE Screw Chassis Ground Chassi...

Page 9: ...otes Equipment must be installed according to the applicable country wiring codes Connect the ground terminal on the power source to the chassis ground terminal on the DVS500 3 2 Dual Redundant Power...

Page 10: ...tput contact that can be used to communicate an alarm to another system e g remote terminal unit if the server stops working The failsafe relay is in open state normally open when the server is powere...

Page 11: ...IP Camera Input The DVS500 can be equipped with IP video inputs 4 port IP Camera Input cards are available with fiber optic SFP based LC connectors or RJ45 connectors All ports support 100Mbps inputs...

Page 12: ...4 relay switch output 30 VDC 1 Amp 50 VAC 5 Amps 6 1 Dry Contact Input Interface Connector Connector Part Number 1727570000 Manufacturer Weidm ller Description Conn Term Block 3 5mm pitch 8POS SN OR...

Page 13: ...Y1 O Common relay output 3 NO_RELAY2 O Normally open relay output 4 COM_RELAY2 O Common relay output 5 NO_RELAY3 O Normally open relay output 6 COM_RELAY3 O Common relay output 7 NO_RELAY4 O Normally...

Page 14: ...568 A wiring standard that characterizes minimum cabling performance specifications required for proper Gigabit Ethernet operation To ensure reliable error free data communications new and pre existi...

Page 15: ...the DVS500 has been designed to meet 8 1 Temperature Humidity 8 2 EMC EMI ESD 1 IEC 61850 3 Electric Utility Substations 2 IEEE 1613 Electric Utility Substations 3 IEC 61000 6 2 Industrial Generic 4...

Page 16: ...ne D C Power ports 2KV line to earth 1KV line to line IEC 61000 4 6 Induced Conducted RFI Signal Ports 10V 10V D C Power ports 10V Earth ground ports 10V IEC 61000 4 8 Magnetic Field Enclosure ports 1...

Page 17: ...x EMI IMMUNITYPE TESTS TEST DESCRIPTION TEST LEVELS IEEE C37 90 3 ESD Enclosure Contact 2KV 4KV 8KV Enclosure Air 4KV 8KV 15KV IEEE C37 90 2 Radiated RFI Enclosure ports 20 V m IEEE C37 90 1 Fast Tra...

Page 18: ...ries info SystemsWithIntelligence com Sales Inquiries sales SystemsWithIntelligence com Product Support support SystemsWithIntelligence com All specifications in this document are subject to change wi...