1. Choose required airflow at normal fan speed as follows:
Set the normal fan speed from a potentiometer on the print card in the unit (see
fig. 13
). The
potentiometer is set by using a screw driver. Each setting corresponds to a different fan speed based
on certain voltage output to the fans (see
table 1
). To get an idea of the airflow corresponding to each
setting see
fig. 14
showing a fan performance diagram displaying performance curves for supply air
and extract air.
DI1
Lo
Hi
GND
12V
AI2
GND
AI3
GND
AI4
GND
GND
AI1
R
N
Earth
R
N
R
N
DI2
220V Aux 2
220V Aux 1
COM
8
8
Table 1
Setting
Voltage output (V)
0 3,63
1 3,99
2 4,35
3 4,72
4 5,09
5 5,45
6 5,82
7 6,17
8 6,54
9 6,9
A 7,27
B 7,64
C 8,00
D 8,36
E 8,73
(Default)
F 10,17
Fig. 13
0
5
10
15
20
25
30
35
40
45
50
55
50
100
150
200
0
250
300
350
400
Q(l/s)
4.1V
6V
1
2
7.7V
10V
1
Fan performance curve extract air
2
Fan performance curve supply air
2. Adjust diffusers and louvers in accordance with commissioning or basic setting (see
"Diffusers/Louvers"). Make sure that the inlet diffusers are set so that the air stream is not lead
towards visible joist, wall etc. close to the diffuser.
Summary of Contents for VR 250 ECH/B
Page 1: ...10 04 17 09 2010 VR 250 ECH B Air Handling Unit Installation description GB GB...
Page 15: ...10 04 2010 09 17 VR 250 ECH B Luftbehandlingsaggregat Installationsbeskrivning GB SE...
Page 29: ...10 04 17 09 2010 VR 250 ECH B Ventilasjonsaggregat Montasjeanvisning NO...
Page 43: ...10 04 17 09 2010 VR 250 ECH B L ftungsger t Installationsanweisung DE...