____________________________________________________________________________________________________
Topvex SR07, SR09, SR11
E
Installation instruction
205870
Systemair AB
14
Power consumption/currents
Model spec.
Voltage
Unit (A)
Heater (kW)
Heater with
separate power
supply (A)
Fuse (A)
Topvex SR07 E HWL/HWH 400V3N~
3,0
-
-
3x10
Topvex SR07 E EL
400V3N~
7,3
3,0
-
3x10
Topvex SR07 E EL
400V3N~
3,0
*12,0
*17,5
3x25
Topvex SR07 E EL
400V3N~
3,0
*12,0
*30 (230V 3~)
3x40
Topvex SR09 E HWL/HWH 400V3N~
5,4
-
-
3x10
Topvex SR09 E EL
400V3N~
11,9
4,5
-
3x16
Topvex SR09 E EL
400V3N~
5,4
*15,0
*22
3x32
Topvex SR09 E EL
400V3N~
5,4
*15,0
*38 (230V 3~)
3x50
Topvex SR11 E HWL/HWH 400V3N~
8,8
-
-
3x13
Topvex SR11 E EL
400V3N~
17,5
6,0
-
3x13
Topvex SR11 E EL
400V3N~
8,8
*12,0
*17.5
3x20
Topvex SR11 E EL
400V3N~
8,8
*24,0
*35
3x50
Topvex SR11 E EL
400V3N~
8,8
*12,0
*30 (230V 3~)
3x63
Topvex SR11 E EL
400V3N~
8,8
*24,0
*60 (230V 3~)
3x80
*Electic heater (above 6 KW) has separate incoming power supply. For 230V3~ a transformer (230V3~ to
400V3~) is needed for the unit supply.
Summary of Contents for Topvex SR07 E