Safety Information 

This machinery must not be put into operation until prior 
to reading mounting instructions and safety information. 
All units are intended for transportation of air in air 
handling systems. They are meant to be used after 
building them into machines or duct systems or after 
contact protection grid have been installed. (EN ISO 
13857). The unit must be connected to ducts on both 
sides (inlet/outlet).  When there is a risk of water 
entering the motor, via the ducts, external protection is 
required. No moving parts shall be accessible after 
installation. The units are not to be used in hazardous 
environments or connected to flues. The TLP units must 
not be installed outdoors. Safety accessories (i.e. motor 
protection, safety grille) may not be dismounted, short 
cut or disconnected. CAUTION Before servicing or 
maintenance, switch off power, (all-pole circuit breaker), 
and make sure the impeller has come to a standstill. 
CAUTION The equipment can have sharp edges and 
corners which may cause injuries.CAUTION, be careful 
when opening the units service-hatches in case the unit 
is mounted with the inspection hatch downward. 

Transportation and Storage 

The TLP units are packaged at the factory to withstand 
normal transport handling. When handling the goods use 
suitable lifting equipment in order to avoid damage to 
equipment and personnel. Do not lift the unit by the 
connecting cable, connection box, impeller or inlet cone. 
Avoid blows and shock loads. Store the unit in a dry 
place protected from weather and dirt until final 
installation

Installation 

Refer to Safety information above. Installation, electrical 
connection and commissioning are only to be carried out 
by authorised personnel and in accordance with 
requirements and demands. Electrical connections are 
made according to the wiring diagram, markings on 
terminal blocks or on cable. All 3 phase units are 
delivered from factory in 400V 3~ connection. CAUTION 
do not use metal compression gland fittings with plastic 
terminal boxes. Use a dummy plug seal for the 
compression gland fitting as well. If the wiring to the K 
fan in the unit is carried out using cables with diameter 
12-14 mm, the entrance bushing must be replaced 
(applies to type K). Assemble the TLP unit in the 
direction of the airflow (see arrow on unit). The unit must 
be installed so that vibrations are not transmitted to duct 
systems or the frame of the building. (Suitable 
accessories like fast clamps and diffusers are available). 
Make sure the assembly of the fan is firmly fixed and 
stable. The smaller sized of TLP 125 to 200, can be 
mounted upside down in false ceilings. In this case the 
heater must be rotated so that the connection box with 
the overheating protection switches face upward or to 
the side. NB TLP 315 cannot be placed upside down. 
The TLP units must be mounted so that service and 
maintenance can be performed easily and safely. 
Disturbing noise can be avoided by installing silencer 
(available accessory).  
For frequency regulation an all pole sinus filter must be 
mounted between motor and frequency controller 

(version all poles: phase to phase, phase to earth). The 
TLP unit is meant for continuous use within the 
temperature range stated.  
The fans inside the TLP unit are equipped with manual 
thermal contacts (reset by cutting the current, motor 
protection SP1), must be taken into consideration when 
connecting surrounding equipment with automatic on/off 
function. 

Operation 

Before initial operation, check the following: 
- Electrical connection has been properly completed. 
- Protective conductor has been connected. 
- Safety devices in place (protection grid) 
- Leftover installation materials and foreign materials 
have been removed from the casing. 
When putting into operation, check thefollowing: 
- Connection data corresponds to the specifications on 
the nameplate: Maximum v6%, -10%, according 
to IEC 38. Rated current must not be exceeded with 
more than 5% at rated voltage. CAUTION when speed 
regulating by reducing the voltage the motor current may 
exceed the rated current at a lower voltage. In this case 
the motor windings are protected by the thermal contact.  
- Smoothness of motor operation, (no abnormal noises). 
-Fans must only be operated by a person that has 
sustainable knowledge or education within this field or 
handling must be carried out with the supervision of such 
person. 

Maintenance, Service and Repair 

Before maintenance, service or repair, make sure that: 
- Power supply is interrupted (all-pole circuit breaker). 
- Fan impeller has come to a complete standstill 
- Observe personnel safety regulations! 
The fan in the unit should be cleaned when necessary, 
at least 1/year to avoid imbalance and unnecessary 
damage to the bearings. Periodical changing of the filter 
inside the unit will prolong the time interval between 
each cleaning of the fan. The fan bearings are 
maintenance free and should only be replaced if 
damaged. Do not use a high-pressure cleaner (steam 
jet) when cleaning the unit. Listen for abnormal operating 
noise. 

Resetting of the thermal trips 

Manual thermal trips (SP1) are reset by disconnecting 
the mains for approx. 10-20min. 
Make sure the unit has not been blocked or that the 
motor protection has tripped. Contact the supplier if the 
motor does not start after controlling and/or resetting the 
motor protection.  

 

Summary of Contents for TLP 125/1,2

Page 1: ...003 TLP Operation and maintenance instructions 3 Drift och underh llsinstruktion 5 K ytt ja huolto ohjeet 7 Instructions d utilisation et d entretien 9 Instrukcja obs ugi i konserwacji 11 13 GB SE FI...

Page 2: ...B Thyristor Fan control C Fan D Heat regulator Pulser or TTC 2000 E Temperature sensor F Heater battery G Relay H Air flow guard pressure sensor A Main switch B Thyristor Fan control C Fan D Heat regu...

Page 3: ...fety of machinery Safety distances to prevent hazard zones being reached by upper or lower limbs EN 60204 1 Safety of machinery Electrical equipment of machines Part 1 General requirements EN 60 335 1...

Page 4: ...smaller sized of TLP 125 to 200 can be mounted upside down in false ceilings In this case the heater must be rotated so that the connection box with the overheating protection switches face upward or...

Page 5: ...erhet Skyddsavst nd f r att hindra fara riskomr den med vre eller nedre extremiteterna EN 60204 1 Maskins kerhet Maskiners elutrustning Del 1 Allm nna fordringar EN 60 335 1 Elektriska hush llsapparat...

Page 6: ...tt Montera enheten s att service och underh ll kan utf ras p ett enkelt och s kert s tt Ljudproblem kan f rebyggas genom installation av ljudd mpare finns som tillbeh r F r frekvensreglering g ller a...

Page 7: ...uus Turvaet isyydet yl raajojen ja alaraajojen ulottumisen est miseksi vaaravy hykkeille EN 60204 1 Koneturvallisuus Koneiden s hk laitteet Osa 1 Yleiset vaatimukset EN 60 335 1 Kotitalouss hk laittei...

Page 8: ...voi asentaa yl salaisin TLP yksik t on asennettava niin ett huolto ja kunnossapitoty t voidaan suorittaa helposti ja turvallisesti H iritsev melu voidaan est asentamalla nenvaimennin saatavana lis va...

Page 9: ...curit pour les membres sup rieurs ou inf rie EN 60204 1 S curit des machines quipement lectrique des machines Partie 1 r gles generals EN 60 335 1 Appareils lectrodomestiques et analogues S curit Par...

Page 10: ...mani re faciliter toute intervention ult rieure de maintenance Des silencieux sp ciaux propos s en option permettent d viter les bruits g nants Dans le cas de variation de fr quence un filtre multipo...

Page 11: ...ze stwa uniemo liwiaj ce si ganie ko czynami g rnymi i dolnymi do stref niebezpiecznych EN 60204 1 Bezpiecze stwo maszyn Wyposa enie elektryczne maszyn Cz 1 Wymagania og lne EN 60335 1 Bezpiecze stwo...

Page 12: ...tym przypadku nagrzewnic nale y tak obr ci aby puszka przy czeniowa zawieraj ca prze czniki zabezpieczenia przed przegrzaniem by a skierowana do g ry lub poziomo na bok UWAGA Centrale TLP 315 nie mog...

Page 13: ...2 440 00 46 222 440 99 www systemair com TLP 125 315 2006 42 EC 2014 35 EU 2014 30 EU EN ISO 12100 2010 EN 13857 EN 60204 1 1 EN 60 335 1 1 EN 60 335 2 80 2 80 EN 50 106 2007 EN 60 335 1 EN 60967 EN 6...

Page 14: ...14 K TLP TLP 125 TLP 200 NB TLP 315 TLP TLP A Main swith A B Thyristor Fan control B C Fan C D Heat regulator D E Temperature sensor E F Heater battery F G Relay G H Air flow guard pressure control H...

Page 15: ...15...

Page 16: ...16 Systemair Sverige AB Industriv gen 3 SE 739 30 Skinnskatteberg Phone 46 222 440 00 Fax 46 222 440 99 www systemair com 205913 26 01 2017...

Reviews: