75
1.15.2
PREHEATING FOR FLOOR
MENU > FOR SERVICEMAN > SPECIAL FUNCTION > PREHEATING FOR FLOOR
Before floor heating, if a large amount of water remains on the floor, the floor may be
warped or even rupture during floor heating operation, in order to protect the floor,
floor drying is necessary, during which the temperature of the floor should be
increased gradually.
During first operation of the unit, air may remain in the water system which can cause
malfunctions during operation. It is necessary to run the air purge function to release
the air (make sure the air purge valve is open).
T1S sets the heat pump leaving water set temperature in preheating for floor mode.
t_FIRSTFH sets the duration of preheating for floor mode.
Preheating for floor
Abreviations:
t_interval_H: Compressor re-start delay in space heating mode.
Whilst the preheating for floor operation is running, the number of minutes that it has been running for and the heat
pump leaving water temperature are displayed on the user interface. During the preheating for floor operation all buttons
except OK are inactivated. To exit the preheating for floor operation, press OK and then select YES when prompted.
1.15.3
FLOOR DRYING UP
MENU > FOR SERVICEMAN > SPECIAL FUNCTION > FLOOR DRYING UP
For newly-installed under-floor heating systems, floor drying up mode can be used to remove moisture from the floor slab
and subfloor to prevent warping or rupture of the floor during floor heating operation. There are three phases to the floor
drying up operation:
Preheating for floor menu
FLOOR DRYING UP menu
12.1 PREHEATING FOR FLOOR
30
°C
72 HOURS
ADJUST
T1S
t_FIRSTFH
ENTER EXIT
12.1 PREHEATING FOR FLOOR
DO YOU WANT TO TURN OFF THE
PREHEATING FOR FLOOR FUNCTION?
CONFIRM
NO
YES
12.2 INPUT DEFINE
ADJUST
TEMP.DOWN TIME(t_DRYD)
WARM UP TIME(t_DRYUP)
KEEP TIME(t_HIGHPEAK)
PEAK TEMP.(t_DRYPEAK)
START TIME
1/2
8
DAYS
5 DAYS
5 DAYS
45°C
21:00
12.2 INPUT DEFINE
ENTER
START DATE
2/2
21
-10-2021
ENTER EXIT