68
1.8
TEMP. TYPE SETTING Menu
MENU > FOR SERVICEMAN > TEMP. TYPE SETTING
The TEMP. TYPE SETTING is used for selecting whether the water flow temperature or
room temperature is used to control the ON/OFF of the heat pump.
When ROOM TEMP. is enabled, the target water flow temperature will be calculated
from climate curves.
For installations without room thermostats, space heating and cooling modes can be
controlled in one of two different ways:
WATER FLOW TEMP. sets whether space heating/cooling modes are controlled according to the leaving water
temperature. If YES is selected, the user is able to set the leaving water temperature on the user interface’s main
screen.
DHW mode is available DHW mode is unavailable
ROOM TEMP. sets whether space heating/cooling modes are controlled according to the room temperature detected
by the temperature sensor inside the wired controller. If YES is selected, the user is able to set the room temperature
on the user interface’s main screen, no matter what is the setting of WATER FLOW TEMP.
DHW mode is available DHW mode is unavailable
DOUBLE ZONE sets whether there are two zones.
WATER FLOW TEMP.
ROOM TEMP.
DOUBLE ZONE
Double zones control
YES
YES
YES
NO
Zone 1: Water temperature control
Zone 2: Climate curve control
YES
NO
NO
YES
Zone 1: Water temperature control
Zone 2: Water temperature control
YES
NO
YES
YES
Zone 1: Water temperature control
Zone 2: Climate curve control
2
TEMP. TYPE SETTING menu
NON
NON
YES
5 TEMP. TYPE SETTING
5.1 WATER FLOW TEMP.
5.2 ROOM TEMP.
5.3 DOUBLE ZONE
ADJUST