30
English
SQ
SQ20 EC
SQ30 EC
SQ40 EC
SQ50 EC
SQ60 EC
SQ70 EC
LO
W
7
7
13
7
9
11
A
0.08
0.08
0.12
0.08
0.1
0.12
Hi
W
23
33
57
25
46
115
A
0.19
0.27
0.46
0.23
0.4
0.86
Low Energy Consumption Fan Motor version
SQ…units can ensure a 0% - 100% constant air flow modulation
(and therefore the thermal and refrigerating capacity) thanks to
the Inverter technology combined with the last generation of high
energy-efficient electric motors (EC brushless). This enables a
constant control on the power supplied according to the room that
needs to be conditioned.
The result is 50% electric energy saving compared to traditional
3-speed asynchronous motors and a considerable reduction
of acoustic emissions. The table below shows the electrical
characteristics of the four types of motors.
NOTE:
• The values showed in the table are reported only at the Low Energy
Consumption Fan Motor. It is necessary to add the control input power
which corresponds to about 5W ("IR Control"), 9W for the pump and
3W or 6W for the valves (4 pipes).
No further electrical connections are necessary (beside power
supply and communication bus) for this unit (fig.39).
All connections between electric components and motor are factory
made.
Low Energy Consumption Fan Motor
English
31
SQ
• The unit control circuit only allows opening of the motorized valve
when the fan motor is working.
• When a lower temperature is required by the thermostats, the
outlet V and H (terminal blocks ref.20) is powered at 230V and
the corresponding chilled water or hot water valve is energized
WARNING: The pump control circuit stops water supply to the cold
valve if an irregular increase of the condensate water level is
detected into the drain pan
• If an irregular increase of the condensate water level is detected
into the drain pan (for example: possible defective drain, pump
malfunction, fan motor not working) the contact of the “safety
level 2” float switch opens to close the regulation valve, stopping
the cold water flow towards the coil and avoiding further
condensation.
Control
The water flow has to be controlled:
• by installing the motorized thermo-electric valves supplied an
accessory
or
• by installing motorized field supplied valves.
Motorized thermo-electric valve assembly and components
(See fig. 28).
Mod.SQ
SQ
20 SQ50 SQ20 SQ60
SQ
30 SQ60 SQ30 SQ70
SQ
40 SQ70 SQ40
2-pipe
4-pipe
Ref. Description
q.ty
q.ty
q.ty
q.ty
a
Actuator
1
1
2
2
b
Valve 1"gas
1
1
Valve 3/4"gas
1
1
1
Valve 1/2"gas
1
c
Shell
1
1
1
1
d
Clips
3
3
3
3
e
Gasket
2
2
4
4
Instructions for mounting of motorized thermoelectric
valve assembly
(see "Components" table)
• The thermo-electric valve must be mounted on the unit after the unit
installation. For this operation follow figures, depending on model.
Assembly (Fig. 30)
With 4–pipes models, first install the valve assembly for the cold
circuit followed by the valve assembly for the hot circuit.
Connect the valve assemble to the coil and
fix it by a 30Nm torque.
Insulate the valve assembly.
Gasket type
Nm
Rubber
10/12
Fibre
25/30
Fit the actuator on the valve body, route the valve cable through the
box and connect it to the terminal block as shown in fig. 37.
• To connect the steel pipes to the system, ensure they are aligned
and supported to avoid excess strain on the unit. If the system is
filled with water, check all fitting seals.
• After ending the hydraulic connections, make sure there are no
leaks Insulate the valve using the shell, fix it by means of the
clips and make sure that all cold parts are insulated (fig. 29 – 30).
• For 4-pipe hot water, repeat all the operations with gas adaptors,
as per the table.
NOTE:
The seal efficiency of the valve assembly is factory tested. Any
system losses are therefore due to an incorrect installation.
Operation of the thermo-electric valve
(See fig. 31)
• This 2- 3-way valve is of the OPEN/CLOSE type with very slow
travel. It is not a modulating valve so it has no PTC.This valve is
driven, as a sensible element, by the ambient thermostat of the
“cassette” unit.
• The 2-way valve is normally closed to the coil with no powered
actuator side. The 3-way valve is normally closed to the coil with
no powered actuator side while is open to the bypass way side.
When the room temperature does not satisfy the thermostat,
the valve opens after about 3 minutes about to allow water to
circulate in the coil.
• If the room temperature satisfies the thermostat or if the electric
power has been switched off, the valve is closed after about 3
minutes towards the coil and is opened towards the bypass.
• If an emergency occurs, the valve may be manually opened,
removing the electric head, unscrewing the ring nut.
When the emergency ends, remember to reset the valve to
automatic operation, repositioning the electric head; failure to do
this can result in condensate formation due the water pipes, even
if the unit is switched off.
• On "IR Control" unit position the water sensor on the inlet pipe
plumbing side.
Instructions for field supplied valves
Water connection
• Install valves following manufacturer's instructions; refer to the
relevant figures for connection to the unit.
• Carefully insulate pipes, valve assemblies and coil connections
(cold water side) to avoid condensation forming on the pipes and
dripping on the false ceiling.
Electrical wiring
• Connect the room control following instructions for the control
used.
ATTENTION:
Route the cables through the electrical box as shown
in fig. 37.
• Connect the valves according to the instructions and the wiring
diagrams attached to the machine documents.
• Valves, closing the unit water inlet when there is no power
supply, must be used.
ON-OFF valves (230V)
• The chilled water valve must be operated by the 230V on-off
signal from terminal V and the hot water valve from terminal H.
• If these connections are not made as described the drain pan
condensate may overflow.
• Valves should open only when the fan is working, that is, when
one of terminals V1, V2, V3 is energized by L mains supply.
• When the system is filled with water, verify all couplings for
tightness.
• The manufacturer does not accept responsibility for the tightness
of the field - installed valve assembly and this is not tested in
the factory.
• He declines any responsibility for non functioning of these
assemblies and for damage due to dripping.
Motorized valve and control
Summary of Contents for SQ20
Page 8: ...8 SQ MAX 200 mm 3 4 5 6 7 8 9 10 11 12 13 14 ...
Page 13: ...13 SQ 38 39 ...
Page 29: ...English 29 SQ IR Control ...
Page 39: ...Italiano 39 SQ IR Control ...
Page 49: ...Français 49 SQ IR Control ...
Page 59: ...Deutsch 59 SQ IR Control ...
Page 69: ...Español 69 SQ IR Control ...
Page 79: ...Nederlands 79 SQ IR Control ...
Page 89: ...ΕΛΛΗΝΙΚΑ 89 SQ IR Control ...
Page 99: ...Português 99 SQ IR Control ...
Page 109: ...Svenska 109 SQ IR Control ...
Page 119: ...Suomi 119 SQ IR Control ...
Page 129: ...Polski 129 SQ IR Control ...
Page 139: ...РУССКИЙ 139 SQ IR Control ...
Page 145: ......