19
Options:
Yes
/
No
.
• Choose bypass damper location if heat exchanger type
Plate
is selected. Default setting is based on unit type.
Supply
/
Extract
• Set actuator type. Default setting is based on unit type.
Range: 0–10 V / 2–10 V / 10–0 V / 10–2 V.
Heater
• Choose heater type. Each selection unlocks additional configuration options. Default setting is based on unit type.
Available types:
None
/
Electrical
/
Water
/
Change-over
.
• Set actuator type. Default value is 0–10 V.
Range: 0–10 V / 2–10 V / 10–0 V / 10–2 V.
• Set circulation pump temperature. Default setting is 10°C. This option is available if
Water
/
Change-over
heater
type is selected.
Range: 0–20°C.
• Set circulation pump stop delay. Default setting is 5 minutes. This option is available if
Water
/
Change-over
heat-
er type is selected.
Range:
Off
/ 1–60 min.
Cooler
• Choose cooler type. Each selection unlocks additional configuration options. Default setting is
None
.
Available types:
None
/
Water
/
Change-over
.
• Set outdoor air temperature interlock. Default setting is 10°C.
Range: 0–20°C.
• Set actuator type. Default value is 0–10 V
Range: 0–10 V / 2–10 V / 10–0 V / 10–2 V.
• Set circulation pump stop delay. Default setting is 5 minutes. This option is available if
Water
/
Change-over
heat-
er type is selected.
Range:
Off
/ 1–60 min.
Extra controller
• Choose extra controller type. Each selection unlocks additional configuration options. Default setting is
None
.
Available types:
None
/
Preheater
/
Heating
/
Cooling
.
• Set temperature set point of the extra controller. Default value is 0°C.
Range: –30°C — 40°C.
• Set P-band. Default setting is 4°C.
Range: 1-60°C.
• Set I-time. Default setting is
Off
.
Range:
Off
/ 1–240 sec.
• Set actuator type. Default value is 0–10 V.
Range: 0–10 V / 2–10 V / 10–0 V / 10–2 V.
• Set circulation pump temperature. Default setting is 0°C. This option is available if
Preheater
controller type is
selected.
Range: 0–20°C.
• Set circulation pump stop delay. Default setting is 5 minutes.
Range:
Off
/ 1–60 min.
4.7.6.4
Control Regulation
Configure how the system is controlled.
| 01_1.8.0