Description of functions
Electrical heating, extract air temperature
control with cascade function.
Function
Start and stop times are set in the
Control panel. To maintain constant
room temperature the RC receives a
signal from GT3 and regulates the VVX
and the electrical heater in sequence.
The GT1 sensor is used to limit the
max and min supply air temperature.
Maximum temperature in the electrical
re-heater is controlled by GTM. GTO
disconnects the heater, gives an alarm
signal and stops the appliance in case
of overheating.
ST1 closes the fresh air damper when
the appliance is stopped. In case of an
unintended stop on the rotor, the RCR
gives an alarm, which is displayed on
the Control panel as an alarm.
Also displayed in the Control panel are
date and time, operating status,
desired and actual room temperature.
GP1 and GP2 give alarm signals when
the actual value exceeds the pre-set
desired value for pressure drop over
the filter.
Designation Name
FF
Exhaust air fan
TF
Supply air fan
GT1
Sensor, supply air
GT2
Sensor, fresh air
GT3
Sensor, extract air
GTM
Sensor, max temperature
in the electrical re-heater.
GTO
Sensor overheating in
heater
GP1
Pressure guard, extract
air filter
GP2
Pressure guard, supply
air filter
RC
Regulator Corrigo E28
RCF
Control box: exhaust air
RCT
Control box: supply air
RCR
Control box for rotor
DR
Motor, rotor
VVX
Heat exchanger rotor
ST1
Damper, fresh air
ST2
Damper, exhaust air