![SystemAir Rotovex 2400 EL Operating And Maintenance Instruction Manual Download Page 7](http://html1.mh-extra.com/html/systemair/rotovex-2400-el/rotovex-2400-el_operating-and-maintenance-instruction-manual_1423012007.webp)
7
GB
External connections
* These inputs may only be wired to voltage free contacts.
All external connections are done in the connection boxes found on each end plate of
the unit. There is a sign on the inside illustrating the various functions and how they
are to be connected.
Terminal block
Description
Remark
13
G
Valve actuator, supply voltage, Heating/cooling
24V AC
14
G0
Valve actuator, supply voltage, Heating/cooling
Neutral
43
AO1
Control signal water heating
0-10V DC
57
AO3
Control signal water cooling
0-10V DC
PE
Water pump, supply voltage. HW Heating
Ground
45
N
Water pump, supply voltage. HW Heating
Neutral
46
L1
Water pump, supply voltage. HW Heating
230V AC
39
DO6
Water pump, control voltage (contactor). Cooling
24V AC, 0,5A
G
DO ref
Water pump, control voltage (contactor). Cooling
33
DO2
Damper, exhaust air
24V AC, 0,5A
34
G0
Damper, exhaust air
Neutral
35
G
Damper, exhaust air
24V AC
36
DO1
Damper, fresh air
24V AC, 0,5A
37
G0
Damper, fresh air
Neutral
38
G
Damper, fresh air
24V AC
56
AI3
Extract air temperature sensor
PT 1000
Agnd
AI ref
Extract air temperature sensor
27
UAI1
Fresh air temperature sensor
PT 1000
Agnd
UI ref
Fresh air temperature sensor
31
AI4
Supply air temperature sensor
PT 1000
32
AI ref
Supply air temperature sensor
55
DO4
DX cooling, step1
24V AC, 0,5A
54
DO5
DX cooling, step2
24V AC, 0,5A
53
DO ref
DX cooling, step1 and 2
*64
DI3
Run-indication/alarm circulation pump Cooling
or
*Ref DI
DI ref
Run-indication/alarm circulation pump Cooling
*47
DI5
Fire alarm
or
*Ref DI
DI ref
Fire alarm
*48
DI6
External stop
*Ref DI
DI ref
External stop
*49
DI7
Extended operation, Normal
*50
DI ref
Extended operation, Normal
*59
DI8
External alarm
*Ref DI
DI ref
External alarm
40
DO7
Sum alarm, A- and B-alarm
G
DO ref
Sum alarm, A- and B-alarm
51
Net +
LON
52
Net -
LON
60
G
Pressure transmitter, supply voltage
24V AC
61
AI1
Pressure transmitter, control signal. Supply air
0-10V DC
62
AI ref
Pressure transmitter
63
AI2
Pressure transmitter, control signal. Extract air
0-10V DC
28
UAI2
Free to use
Agnd
UI ref
Free to use
58
UAI3
Free to use
Agnd
UI ref
Free to use
*Ref DI
DI ref
Is used together with UDI
By spring-loaded
damper, connect
33/35
By spring-loaded
damper, connect
36/38