6
| Description
5.5.1
Sensor control module for differential pressure and volume PCA1000/6000D2
The factory setting of the controller is CAV (constant air volume). The measured value is compared with the setpoint
value. The controller adjusts the 0-10 V controlled output for the EC motor to keep the air volume constant. The specific
characteristics of the inlet cone size are considered in the k-factor. Table 7
K-factor MUB-CAV/VAV
, page 6. For more
detailed information of the controller module (PCA1000/6000D2), see operating manual of the controller.
Table 7 K-factor MUB-CAV/VAV
025 315EC
100
042 400EC
172
042 450EC-K
235
062 560EC
418
100 630EC
456
025 355EC
143
042 450EC
238
042 500EC
266
062 630EC
500
100 710EC
550
5.6
Description MUB/F
The fan is equipped with high-temperature motors for temperature classification F400/120 min, in single and two-
speed versions.
The MUB/F smoke extract fans are suitable for the exhaust of hot smoke gases (once) and for daily ventilation require-
ments. After using the fan for the exhaust of hot smoke gases it has to be renewed.
Table 8 Dimensions MUB/F
[mm]
A
B
C
D
E
F
A
F
E
C
B
D
MUB/F 042 400
670
670
590
548
400
783
MUB/F 042 450
670
670
590
548
400
783
MUB/F 062 500
800
800
720
676
560
915
MUB/F 062 560
800
800
720
676
560
915
MUB/F 062 630
800
800
720
676
630
915
| 007