7.3.5.1 Inspection
• Check the coil fins for any damage;
• Check if refrigerant is not leaking;
• Check the dip dray and drain, clean if necessary;
7.3.5.2 Cleaning
• Use the vacuum cleaner to remove dust from the inlet side of you can blow them with compressed
air from the outlet side;
• Use hot water mixed with non corrosive cleaning medium and rinse using water. Any corrosion should
be cleaned off immediately and the surface treated.
7.3.6 Checking the condenser
A brazed plate heat exchanger is used as the condenser to transfer heat from refrigerant gas to the water
system. Inspection and cleaning procedure is similar to the evaporator coil maintenance.
7.3.6.1 Inspection
• Check the heat exchanger cover for any damage;
• Check if water is not leaking;
• Check if refrigerant is not leaking;
7.3.6.2 Cleaning
• Use hot water mixed with non corrosive cleaning medium and rinse using water. Any corrosion should
be cleaned off immediately and the surface treated.
7.3.7 Checking the damper
A faulty damper can give rise to disturbances that may result in serious problems. Make sure to check all
three dampers.
• Check operation of the damper actuator.
• Check that the damper tightens when closed. If not, adjust the damper actuator to make the damper
tight (does not apply to trim dampers).
• Check the sealing strips.
• If the damper does not operate, check that nothing is stuck between the drive mechanism and damper
blades to interfere with the damper function.
Operation and Maintenance Instructions