6.3.1 Settings menu
Display/Mask No.
Description
Set user menu (SET1)
Set user menu (SET3)
The unit has adaptive heating capacity.
The unit can regulate capacity in three ways:
• Delta T extract-exhaust air. Unit will try to
maintain set value (default 18°C)
• Delta T water in-out. Unit will try to maintain
settled value (default 6°C)
• By heating curve. Possible to choose from 5
heating curves.
Note:
The regulation type can be selected from Main
menu in Unit settings.
Set user menu (SET2)
Ventilation process can be regulated in two ways:
1. By differential pressure on duct (VAV);
2. By constant air flow (CAV).
Note:
The regulation type can be selected from Main
menu In Unit settings.
Note:
In “Summer mode”, when the ventilation process is
switched from the unit to fire/smoke fan, regulation
will be carried by differential pressure on duct.
Set user menu (SET4)
1. Antifreeze prevention helps to protect evaporator
from icing and saves energy not letting
compressor work at very low evaporation
temperatures.
2. High pressure prevention helps to protect
compressor from very high condensing
temperatures.
Note:
It is strongly recommended to keep factory settings
for proper and safe operation.
Operation and Maintenance Instructions
209531
13
Systemair AB