2 / 8 | PP-52_201504 | DKIR1 & DKIS1
Fig. 1: Installatin of the round smoke damper DKIR1 onto and into
the duct running through the vertical supporting construction
(v
ed
- see the fire resistivity on the page 3)
NOTE: Installation onto the duct - distance between lower edge
of the open blade and bottom wall of the duct must be more
than 100 mm.
Fig. 2: Installatin of the rectangular smoke damper DKIS1 onto and
into the duct running through the vertical supporting construction
(v
ed
- see the fire resistivity on the page 3)
NOTE: Installation onto the duct - distance between lower edge
of the open blade and bottom wall of the duct must be more
than 100 mm.
Note
• Caution: Main power supply voltage !
• Parallel connection of several actuators possible.
Power consumption and switching thresholds
must be observed!
!
S1 S2 S3 S4 S5 S6
<3°
<87°
3
2
1
N
L 1
Note
• Supply via safety isolation transformer
• Parallel connection of several actuators possible.
Power consumption and switching thresholds
must be observed!
!
S1 S2 S3 S4 S5 S6
<3°
<87°
3
2
1
N
L 1
S1 S2 S3 S4 S5 S6
<3°
<87°
3
2
1
T
~
~
Application with the SBSE-Control
damper control and monitoring system
Connecting lead with plugs for linking to the communication
and power unit BKNE230-24
Application with the SBSE-Control
damper control and monitoring system
Connecting lead with plugs for linking to the communication
and power unit BKNE230-24
S1 S2 S3 S4 S5 S6
<3°
<87°
3
2
1
T
~
~
Fig. 3: Connection of the actuator BELIMO BLE 230
Fig. 4: Connection of the actuator BELIMO BE 230-12
Fig. 5: Connection of the actuator BELIMO BLE 24
Fig. 6: Connection of the actuator BELIMO BE 24-12-ST