SystemAir DKIR1 Original Installation, Operation And Maintenance Manual Download Page 4

4 / 8    |    PP-52_201504    |    DKIR1 & DKIS1

Fig. 10: Dimensions of the rectangular smoke damper with 

> 1200 mm up to 1500 × 800 mm

NOTE: These smoke dampers have flanges width 40 mm.

L

=360

R

1

R

2

W

×

H

(

W

+80)×(

H

+80)

8,8×11,8

W

1

Warnings

Some damper parts can have sharp edges – therefore it 

is necessary to use gloves during damper installation and 

manipulation.  

In order to prevent an electric injury, fire or any other damage 

which could result from incorrect damper usage and operation,  

it is important to:
1.  Install the damper in accordance with the installation manual 

and by a properly trained employee.

2.  Execute the damper inspection in accordance with this 

installation, operation and maintenance manual.

3.  Before you can install the smoke damper, it‘s functionality 

must be checked according to chapter 3 Check of the 

functionality.  

This procedure prevents installation of a damper that has 

been damaged during transportation or handling.

Do not install functionless fire dampers!

Operating conditions

Smoke dampers are part of the Smoke and Heat Exhaust 

Ventilation System (SHEVS). Functionality of the smoke damper  

is following. In case of fire damper:
• 

opens and removes the heat and smoke through a special fan 

from  the fire compartment affected by fire or

•  closes and prevents the spread of smoke and heat in the fire 

compartment unaffected by fire.

All smoke dampers have electric actuator as standard. They are 

designed to be installed in the SHEVS ducts in locations that are 

protected from weather.
Systemair smoke dampers are passive in terms of noise. There is 

increased noise only when closing or opening the damper in case 

of inspection or fire (and it takes less than 60 seconds).

1 Installation

The installation must be done as follows:

• 

Duct connected to the damper must be supported or 

suspended so that the damper do not bear its weight.  

The damper must not bear any part of the supporting 

construction. This could lead to damage and subsequent failure 

of the damper.

• 

Actuator can be on either side of the supporting construction,  

but it must be placed so that it is easy to access for inspection  

and repairs.

• 

Distance between dampers and building structures, distribution 

technology and ventilation equipment must be large enough 

for reliable performance of the installation, functional testing, 

inspection and repair.

• 

The distance between the dampers must be at least 200 mm 

according to EN 1366-10.

• 

The distance between dampers and the wall or ceiling must be 

at least 200 mm according to EN 1366-10.

• 

The gap between the damper and the selfstanding grill (when 

installed) must be at least 200 mm according to EN 1366-10. 

Otherwise the damper must be tested together with the grill.

• 

The smoke dampers must be installed with horizontal blade axis.

• 

Before the installation of the smoke damper, it‘s functionality 

must be tested according to the chapter 3 Check of the 

functionality.

DO NOT INSTALL NONFUNCTIONAL SMOKE DAMPERS!

• 

Changes of smoke damper functionality, caused by transport 

or installation, aren´t reclaimable after the installation 

(deformations, damages, mechanical damage of the sealing 

material, foreign objects which can constrain the blade, wrong 

handling of the activating mechanism etc.)

• 

Before connection of the smoke damper into the ductwork, 

smoke damper‘s functionality must be checked again 

(according to chapter 3 Check of the functionality).

IT IS NOT POSSIBLE TO CLAIM FAULTY FUNCTIONALITY CAUSED 

BY PRODUCTION, TRANSPORTATION OR INSTALLATION AFTER 

CONNECTING THE DUCTS TO THE SMOKE DAMPER!

During installation, it is necessary to protect the damper 

mechanism and its interior against dirt. The blade must be  

in the closed position. It is necessary to avoid deformation  

of the damper. Installation and setup of the dampers is always 

determined by SHEVS project plans that must comply with the 

applicable regulations. 
The smoke dampers DKIR1 must be installed according to Fig. 1, 

the smoke dampers DKIS1 must be installed according to Fig. 2.
After damper installing into the SHEVS duct it is necessary 

to connect electrical installation that must be done only by 

authorized persons – connection has to be done according to  

Fig. 3 - 7.  The actuators have two microswitches indicating  

the open and closed positions of the blade - see Fig. 3 - 6.
Setup, install, repair, overhaul and inspections of the dampers 

must be done only by the manufacturer or by the personnel 

Summary of Contents for DKIR1

Page 1: ...SMOKE CONTROL DAMPERS Round DKIR1 and Rectangular DKIS1 ORIGINAL INSTALLATION OPERATION AND MAINTENANCE MANUAL EVERY SMOKE DAMPER NEEDS TO BE INSTALLED IN ACCORDANCE WITH THIS MANUAL 1396 CPD 0058 ...

Page 2: ...ion of several actuators possible Power consumption and switching thresholds must be observed S1 S2 S3 S4 S5 S6 3 87 3 2 1 N L 1 Note Supply via safety isolation transformer Parallel connection of several actuators possible Power consumption and switching thresholds must be observed S1 S2 S3 S4 S5 S6 3 87 3 2 1 N L 1 S1 S2 S3 S4 S5 S6 3 87 3 2 1 T Application with the SBSE Control damper control a...

Page 3: ...rs hereafter dampers circular DKIR1 and rectangular DKIS1 the products of Systemair It contains basic information and recommendations regarding the installation use and inspections that need to be followed to ensure proper and smooth operation of the dampers Resistance class E600 120 ved i o S500C10000 AA single is valid for all nominal dimensions of round dampers see Fig 8 and for nominal dimensi...

Page 4: ...inspection and repairs Distance between dampers and building structures distribution technology and ventilation equipment must be large enough for reliable performance of the installation functional testing inspection and repair The distance between the dampers must be at least 200 mm according to EN 1366 10 The distance between dampers and the wall or ceiling must be at least 200 mm according to ...

Page 5: ...24 months starting on the date of product shipment by an exceptional agreement this period can be up to 30 months starting on the date of shipment 2 The product is tested in the production factory before the shipment The producer guarantees that the product features shall be in accordance with the related technical standards during the whole warranty period assuming that the customer uses it in a ...

Page 6: ...of the following inspection after deficiencies elimination Inspection technician s signature Periodic damper inspection at least once in 12 months Date Description of found defects and date of the following inspection after deficiencies elimination Inspection technician s signature OPERATING DIARY ...

Page 7: ...S1 PP 52_201504 7 8 Periodic damper inspections at least once in 12 months Date Description of found defects and date of the following inspection after deficiencies elimination Inspection technician s signature ...

Page 8: ...nkovo 146 Slovakia 1396 CPD 0058 EN 12101 8 Smoke damper round DKIR1 DN rectangular DKIS1 WxH Operational reliability cycling 10 200 cycles passed Fire resistance E600120 ved i o S500C10000AAsingle or E600120 ved i o S1500C10000AAsingle see the page 3 maintenan of t cross section under E integrity E 600 C smoke leakage S 500 Pa and 1500 Pa see the page 3 mechanical stability under E cross section ...

Reviews: