DKIR1 & DKIS1    |    PP-52_201504    |    3 / 8    

BKNE230-24

1

2

3
4

5
6

7

a

b

BE(G)24-ST, BE24-12-ST

M

AC 230 V

2-wire conductor

to BKSE24-6

Nothing must

be assigned

to terminals

1 to 5

The device contains no

parts  which  can  be

replaced or repaired by

the user.

Displays

LED
yellow
yellow
green
green
yellow 
green
yellow

w1098402

Function

fault

flashing at double

or

power failure

dark

+green

Status

damper moving to OPEN
damper open
damper moving to CLOSED
damper closed

flashing light

flashing light

steady light

steady light

frequency

Fig. 7: Connection and display of the supply and communication unit BKNE230-24 

Introduction

Instructions for installation, operation 

and control refers to the smoke dampers 

(hereafter dampers) circular DKIR1  

and rectangular DKIS1, the products  

of Systemair. It contains basic information 

and recommendations regarding the 

installation, use and inspections that need 

to be followed to ensure proper  

and smooth operation of the dampers.

Resistance class E

600

120 (v

ed

 i ↔ o) 

S500C

10000

 AA single is valid for all 

nominal dimensions of round dampers 

(see Fig. 8) and for nominal dimensions  

of rectangular dampers where  

> 1200 mm (see Fig. 10).

Resistance class E

600

120 (v

ed

 i ↔ o) 

S1500C

10000

 AA single is valid only for 

rectangular dampers with nominal 

dimensions 

H

 × 

from

 

200 × 200  

up to 1200 × 800 mm (see Fig. 9).

Fig. 8: Dimensions of the round smoke damper

Fig. 9: Dimensions of the rectangular smoke damper for nominal dimensions  

× 

H

 = 200 × 200 up to 1200 × 800 mm

NOTE: These smoke dampers have flanges width 20 mm.

ø

DN

+4

5

W

1

L

=400

R

2

ø

D

45

45

R

1

L

 = 325

R

2

W

×

H

(

W

+40)×(

H

+40)

W

1

8,8×11,8

R

1

Summary of Contents for DKIR1

Page 1: ...SMOKE CONTROL DAMPERS Round DKIR1 and Rectangular DKIS1 ORIGINAL INSTALLATION OPERATION AND MAINTENANCE MANUAL EVERY SMOKE DAMPER NEEDS TO BE INSTALLED IN ACCORDANCE WITH THIS MANUAL 1396 CPD 0058 ...

Page 2: ...ion of several actuators possible Power consumption and switching thresholds must be observed S1 S2 S3 S4 S5 S6 3 87 3 2 1 N L 1 Note Supply via safety isolation transformer Parallel connection of several actuators possible Power consumption and switching thresholds must be observed S1 S2 S3 S4 S5 S6 3 87 3 2 1 N L 1 S1 S2 S3 S4 S5 S6 3 87 3 2 1 T Application with the SBSE Control damper control a...

Page 3: ...rs hereafter dampers circular DKIR1 and rectangular DKIS1 the products of Systemair It contains basic information and recommendations regarding the installation use and inspections that need to be followed to ensure proper and smooth operation of the dampers Resistance class E600 120 ved i o S500C10000 AA single is valid for all nominal dimensions of round dampers see Fig 8 and for nominal dimensi...

Page 4: ...inspection and repairs Distance between dampers and building structures distribution technology and ventilation equipment must be large enough for reliable performance of the installation functional testing inspection and repair The distance between the dampers must be at least 200 mm according to EN 1366 10 The distance between dampers and the wall or ceiling must be at least 200 mm according to ...

Page 5: ...24 months starting on the date of product shipment by an exceptional agreement this period can be up to 30 months starting on the date of shipment 2 The product is tested in the production factory before the shipment The producer guarantees that the product features shall be in accordance with the related technical standards during the whole warranty period assuming that the customer uses it in a ...

Page 6: ...of the following inspection after deficiencies elimination Inspection technician s signature Periodic damper inspection at least once in 12 months Date Description of found defects and date of the following inspection after deficiencies elimination Inspection technician s signature OPERATING DIARY ...

Page 7: ...S1 PP 52_201504 7 8 Periodic damper inspections at least once in 12 months Date Description of found defects and date of the following inspection after deficiencies elimination Inspection technician s signature ...

Page 8: ...nkovo 146 Slovakia 1396 CPD 0058 EN 12101 8 Smoke damper round DKIR1 DN rectangular DKIS1 WxH Operational reliability cycling 10 200 cycles passed Fire resistance E600120 ved i o S500C10000AAsingle or E600120 ved i o S1500C10000AAsingle see the page 3 maintenan of t cross section under E integrity E 600 C smoke leakage S 500 Pa and 1500 Pa see the page 3 mechanical stability under E cross section ...