Page 48
Technical data
AQVC
Al/Cu
Weight distribution
Ope-
rating
weight
Ship-
ping
weight
P1-P4 coordinates* CG coordinates
F1
F2
F3
F4
a
b
x
y
kg
kg
kg
kg
kg
kg
mm
mm
mm
mm
85
385
384
101
100
971
971
1039
1382
547
1584
95
391
390
101
101
983
983
1039
1382
547
1587
105
395
403
104
111
1013
1013
1039
1382
555
1578
115
408
407
114
114
1043
1043
1039
1382
547
1569
125
384
385
148
149
1066
1066
1039
1982
549
1920
140
406
405
166
165
1142
1142
1039
1982
547
1897
AQVC 85 - 140 Al/Cu Version BLN/ELN/HT
AQVC
Cu/Cu
Weight distribution
Ope-
rating
weight
Ship-
ping
weight
P1-P4 coordinates* CG coordinates
F1
F2
F3
F4
a
b
x
y
kg
kg
kg
kg
kg
kg
mm
mm
mm
mm
85
438
437
155
154
1183
1183
1039
1382
546
1511
95
444
443
155
154
1196
1196
1039
1382
546
1514
105
453
468
162
178
1261
1261
1039
1382
560
1499
115
479
477
186
185
1326
1326
1039
1382
546
1484
125
454
454
217
217
1342
1342
1039
1982
548
1830
140
499
496
258
256
1509
1509
1039
1982
546
1796
AQVC 85 - 140 Cu/Cu Version BLN/ELN/HT
* Dimensions are referred to unit with antivibration mounted isolators.
AQVC
MCHX
Weight distribution
Ope-
rating
weight
Shipping
weight
P1-P4 coordinates* CG coordinates
F1
F2
F3
F4
a
b
x
y
kg
kg
kg
kg
kg
kg
mm
mm
mm
mm
85
358
358
74
74
864
864
1039
1382
547
1635
95
364
364
74
74
876
876
1039
1382
547
1637
105
366
366
74
74
880
880
1039
1382
549
1639
115
368
368
74
74
884
884
1039
1382
547
1639
125
349
351
113
115
928
928
1039
1982
550
1985
140
354
354
114
114
935
935
1039
1982
547
1988
AQVC 85 - 140 MCHX
AQVC
Line length
ø Suction line
ø Liquid line
R410A
m
inch
mm
inch
mm
kg/m
85
10
1”3/8
34,93
7/8”
22,23
0,34
20
1”3/8
34,93
7/8”
22,23
0,34
30
1”3/8
34,93
7/8”
22,23
0,34
95
10
1”3/8
34,93
7/8”
22,23
0,34
20
1”3/8
34,93
7/8”
22,23
0,34
30
1”3/8
41,28
7/8”
22,23
0,35
105
10
1”3/8
34,93
7/8”
22,23
0,34
20
1”3/8
34,93
7/8”
22,23
0,34
30
1”5/8
41,28
7/8”
22,23
0,35
115
10
1”3/8
34,93
1”1/8
28,58
0,53
20
1”3/8
34,93
1”1/8
28,58
0,53
30
1”5/8
41,28
1”1/8
28,58
0,54
125
10
1”3/8
34,93
1”1/8
28,58
0,53
20
1”3/8
34,93
1”1/8
28,58
0,53
30
1”5/8
41,28
1”1/8
28,58
0,54
140
10
1”3/8
34,93
1”1/8
28,58
0,53
20
1”5/8
41,28
1”1/8
28,58
0,54
30
1”5/8
41,28
1”1/8
28,58
0,54
AQVC Refrigerant Lines
AQVC125: Max distance: consider 30mt. 30mt Suction line + 30mt Liquid line.
Each refrigerant circuit needed to add 0.53kg / mt of distance. In example in case of 30mt distance between AQVC and evaporator, for
each circuit consider 30x0.53kg = 15.9kg per circuit.
Summary of Contents for AQVC 105
Page 60: ...English Page 59 Note...
Page 61: ...Page 60 Note...