3.2 Extended running
Digital inputs can be used to force the unit to start although the timer says the running mode should be
“Off”.
Configuration > Functions > Function Activation
> Extended operation > “Yes”
The unit can be set for extended running at one or all available speeds
Configuration > Functions > Extended operation >
Digital input of the controller must be assigned for extended running switch
Configuration > I/O allocation settings > Digital inputs >
If momentary switch is used to activate the function, the time for extended operation can be set
Time settings > Extended operation stop delay >
Then time is set to 0min, the unit will only run if the digital input is closed.
3.3 External stop
The ”External
stop
”
signal will stop the unit, even if the timer or any of the extended operation signals
says it should stay in running mode.
Configuration > Functions > Function Activation
> External stop > “Yes”
Digital inputs of the controller must be assigned for external stop function
Configuration > I/O allocation settings > Digital inputs >