Access V4.X Configuration manual
11 (33)
2019-05-13
If required sequence overlapping or dead band can be set by
adjusting “Start Heating” and “Start
Cooling” sequence parameters. Adjustable range is
-100% .. +100%. Negative starting point will create
sequence overlap while positive starting point will delay start of the selected sequence.
Position
Heating
Cooling
Start
Heating
Start
Cooling
Name
SEQ-A
2
Off
50% 0%
0%
Heating
SEQ-B
1
1
0%
0%
Exchanger
SEQ-C
Off
2
0%
-25% 0%
Cooling
SEQ-D
Off
Off
0%
0%
Recirculation 1
SEQ-E
Off
Off
0%
0%
Recirculation 2
SEQ-F
Off
Off
0%
0%
Fan heating/cooling
SEQ-G
Off
Off
0%
0%
Heating 2
SEQ-H
Off
Off
0%
0%
Cooling 2
SEQ-I
Off
Off
0%
0%
Exchanger extract
SEQ-J
Off
Off
0%
0%
Extra heating/cooling capacity