4/46 |
FDR-3G…OF
• Low pressure drop
• Changeable mechanism
• Inspection opening built-in
• Great variety of installations rated up to EI120S
Activation Types
• H0-OF
Overflow fire damper with an activation mechanism with a cover, manual crank and with a spring return release
mechanism activated by a fusible thermal link set to 74°C (on demand 100°C).
• H2-OF
Overflow fire damper with an activation mechanism H0-OF + open and closed indication with AC 230 V or AC/DC 24 V
contact switches.
• H5-2-OF
Overflow fire damper with an activation mechanism H0-OF + a AC/DC 24 V electromagnetic release mechanism in the
impulse connection (release takes place when the electromagnet is activated) + open and closed indication with AC
230 V or AC/DC 24 V contact switches.
• H6-2-OF
Overflow fire damper with an activation mechanism H0-OF + an AC 230 V electromagnetic release mechanism in the
impulse connection (release takes place when the electromagnet is activated) + open and closed indication with AC
230 V or AC/DC 24 V contact switches.
• B230T-OF or G230T-OF
Overflow fire damper with an activation mechanism with a Belimo or Gruner spring return actuator (AC 230 V) with
electro-thermal fuse 72°C and auxiliary switches.
• B24T-OF or G24T-OF
Overflow fire damper with an activation mechanism with a Belimo or Gruner spring return actuator (AC/DC 24 V) with
electro-thermal fuse 72°C and auxiliary switches.
• BSD230T-OF or GSD230T-OF
Overflow fire damper with Smoke Detector fitted activation mechanism (AC 230 V) with a Belimo or Gruner spring
return actuator with an electro-thermal fuse 72°C and auxiliary switches, with a Belimo supply and communication unit
or Gruner power supply unit (Actuator powered through transformer and Smoke Detector AC/DC 24 V).
• BSD24T-OF or GSD24T-OF
Overflow fire damper with Smoke Detector fitted activation mechanism (AC/DC 24 V) with a Belimo or Gruner spring
return actuator with an electro-thermal fuse 72°C and auxiliary switches, with a Belimo supply and communication unit
or Gruner power supply unit (Actuator powered through Smoke Detector AC/DC 24 V).
Design
Fire dampers have casings made from galvanized sheet metal. Blades from non-asbestos insulants have a rubber seal
for cold smoke and an intumescent seal, that expands in a fire situation. Overflow fire damper is equipped on both
ends with galvanized sheet metal Grilles mounted on sheetmetal duct extensions.
Material Composition
The product contains galvanized sheet metal, calcium silicate board, fireproof carbon fiberglass, polyurethane foam and
ethylene-propylene rubber. These are processed in accordance with local regulations. The product contains no
hazardous substances, except for the solder in the thermofuse, which contains a milligram of lead.
List of Accessories
Detailed information about accessories for FDR-3G...OF is available in SystemairDESIGN under Fire Damper Accessories.
• AM-FD: Activation Mechanisms
• CBR-FD: Cover Boards
Summary of Contents for A-FDR-3G-OF
Page 1: ...FDR 3G OF Overflow Fire Damper FDR 3G...
Page 13: ...13 46 FDR 3G OF 250 DN 630 Standardardly in position B On demand in position L T...
Page 17: ...17 46 FDR 3G OF...
Page 18: ...18 46 FDR 3G OF...
Page 21: ...21 46 FDR 3G OF...
Page 22: ...22 46 FDR 3G OF...
Page 25: ...25 46 FDR 3G OF...
Page 26: ...26 46 FDR 3G OF...
Page 29: ...29 46 FDR 3G OF...
Page 30: ...30 46 FDR 3G OF...
Page 46: ...Systemair DESIGN 2021 04 27 Handbook_FDR_3G_OF_en GB...