background image

13

fantech

AIRFLOW ADJUSTMENT & BALANCING

BALANCING THE AIRFLOWS IS CRUCIAL TO ENSURE OPTIMAL OPERATION OF THE UNIT. IF THE AIRFLOW IS NOT PROPERLY BALANCED, THE 
FOLLOWING ISSUES MAY OCCUR:

•  SIGNIFICANT POSITIVE OR NEGATIVE PRESSURE INSIDE THE HOUSE
•  UNIT’S EFFICIENCY MAY BE NEGATIVELY AFFECTED
•  UNIT’S DEFROST MAY NOT WORK EFFECTIVELY
•  CAN LEAD TO AIR LEAKS OR BACKDRAFTING OF ANY COMBUSTION APPLIANCES.

The airflow adjustment and balancing procedure consists of adjusting the fresh airflow to make sure it meets the requirements for the building and then 
balance the system to make sure there is an equal amount of stale air being exhausted. In the case that the airflow is not exactly the same, it is 
recommended to have a higher stale airflow of up to 10% in colder climates to ensure that the temperature of the fresh airflow coming from the outside 
is as close to the room temperature as possible.

GENERAL PREPARATION:

Before performing the adjustment and balancing for unit, make sure to check the following:

•  Seal all the ductwork
•  Fully open all dampers (if present)
•  Turn off all other exhaust appliances such as range hood, dryers, bathroom fans, etc.
•  If performing balancing during cold weather, make sure the unit is not operating in defrost mode.
•  If the installation type is Simplified or Partially Dedicated, make sure that the furnace/air handler blower is operating at normal speed during 

the balancing sequence.

•  When reading with a mechanical type manometer (Magnehelic), make sure the manometer is placed on a level surface

For optimal performance, ERV unit should be re-balanced after a major renovation or after the installation of extra grilles or registers.

• 

In cold climates, continuous excessive positive pressure inside the house may drive moisture inside the external walls of the 
house. Moisture present inside the external wall may condense if the outside temperature is cold enough and can cause damage 
to structural components. A symptom of excessive positive pressure inside a house is frozen door locks.

•  Continuous excessive negative pressure can have undesirable effects. In some geographic locations, negative pressure can 

increase the infiltration of soil gases such as methane and radon. Negative pressure is also undesirable where combustion 
equipment is present and may cause back drafting of the combustion gases.

ADJUSTING AIRFLOWS USING INTEGRATED BALANCING SYSTEM

Adjustable dampers are integrated into the Fresh Air to Building and the Stale Air to Outside duct connections. Those dampers replace the installation of 
separate back draft and balancing dampers in the duct line.

The integrated dampers are preset at the fully opened position. In order to reduce the amount of airflow, turn the adjustable lever using a flat screw driver 
by turning it counter clock wise. Turning the lever clockwise may damage the plastic screw head. Follow the balancing steps to properly adjust the airflow.

Summary of Contents for 463278

Page 1: ...Lenexa KS 66215 Tel 800 747 1762 Fax 800 487 9915 Canada 50 Kanalflakt Way Bouctouche NB E4S 3M5 Tel 800 565 3548 Fax 877 747 8116 VER200 Energy Recovery Ventilator Your ventilation system should be...

Page 2: ...on equipment i e Gas Furnaces Oil Furnaces Wood Stoves etc Products are designed and manufactured to provide reliable performance but they are not guaranteed to be 100 free of defects Even reliable pr...

Page 3: ...Installing the ducting to the weatherhood 9 INTERIOR DUCTING INSTALLATION General Tips 10 Installing duct to ERV 10 Supply Exhaust Air Grilles Location 10 ERV INSTALLATION 11 AIRFLOW ADJUSTMENT BALAN...

Page 4: ...21 53 25 60 28 501 1000 47 93 45 21 53 24 60 28 68 31 75 35 1001 1500 94 139 60 28 68 31 75 35 83 38 90 42 1501 2000 140 186 75 35 83 38 90 42 98 45 105 49 2001 2500 187 232 90 42 98 45 105 49 113 52...

Page 5: ...y areas of the home requiring local exhaust bathroom kitchen laundry room 2 Fresh air is distributed directly to habitable rooms in the house bedrooms living room 3 The ERV s airflow must be balanced...

Page 6: ...g any installation type requiring the use of the furnace interlock Fantech energy recovery ventilators ERV that use a supply fan shutdown for frost prevention do not include an outdoor air motorized d...

Page 7: ...an outdoor air motorized damper If you are using a simplified installation i e connecting the ERV supply air duct to a furnace s return air duct the ERV must operate continuously When the ERV is turne...

Page 8: ...urn ERV Furnace ducting for Simplified Installation Option 2 Suggested installation for When bathroom and kitchen already have local exhaust system May be suitable for retrofitting Benefits Least expe...

Page 9: ...liner which acts as a vapor barrier must be completely sealed to the outer wall and the ERV using tape and or caulking A good bead of high quality caulking preferably acoustical sealant will seal the...

Page 10: ...exible duct to prevent leakage between the ducting and the duct connection In the case of solid ducting slide duct over duct connection screw in place and seal SUPPLY AIR GRILLES LOCATION In homes wit...

Page 11: ...etop fan Central vacuum system Bathroom exhaust fans unless they are specifically designed for this purpose These appliances may cause lint dust or grease to collect in the ERV damaging the unit Mount...

Page 12: ...ke sure to place gasket between the unit and the drain nipple inside the unit 3 Secure the drain nipple using the nutsert 4 Install the drain hose making a P trap secure the condensate line drain conn...

Page 13: ...is operating at normal speed during the balancing sequence When reading with a mechanical type manometer Magnehelic make sure the manometer is placed on a level surface For optimal performance ERV uni...

Page 14: ...rflow may affect the other airflow as well It is recommended to check each airflow again to make sure the value did not change dramatically during the balancing procedure Make adjustments as necessary...

Page 15: ...een LCD ECO mode selects the best operating mode and speed for the season minimizing energy use associated with ventilation Set preferred indoor relative humidity range and ventilation mode for day an...

Page 16: ...e system Use in bathroom kitchen laundry room WALL CONTROLS CONT D MDEH SERIES FEATURES CONNECT TO MDEH1 Rotary dial Dehumidistat Multiple units can be used We recommend setting the relative humidity...

Page 17: ...17 fantech WIRING DIAGRAM Observe polarity on all accessory controls where applicable...

Page 18: ...ONNECTION TO A COOLING SYSTEM On some newer furnaces and older thermostats energizing the R and G terminal at the furnace has the effect of energizing the Y at the thermostat and thereby turning on th...

Page 19: ...Inadequate power supply at site Have electrician check supply voltage Ductwork is restricting airflow Check duct installation Improper speed control setting Increase the speed of the ERV i e change u...

Page 20: ...damages incurred in the use of the ventilation system Fantech is not responsible for providing an authorized service centre near the purchaser or in the general area Fantech reserves the right to sup...

Page 21: ...r core s air inlets facing down place it in a large sink bathtub or shower 4 Pour clean tap water through the face of the core facing upwards until it runs clear Ensure the entire surface is rinsed 5...

Page 22: ...itch 410867 6 Collar 6 Oval w Hole 413893 7 Collar 6 Oval w o Hole 413894 9 Kit RV CTRL Replacement H F 428252 10 Kit Drain Plug 40315 11 Auto Transformer 411963 12 Control Switch 410213 13 Screw Set...

Page 23: ...23 fantech Notes...

Page 24: ...make technical changes For updated documentation please refer to www fantech net Fantech Fantech se r serve le droit de faire des changements tech niques Pour de la documentation jour s il vous pla t...

Reviews: