background image

19

fantech

TROUBLESHOOTING

Problem

Causes

Solutions

Air is too dry

Dehumidistat control is set too low

Increase the desired level of humidity. Change ventilation mode from 
continuous mode to standby.

ERV out of balance

Have contractor balance ERV airflows

Air is too humid

Dehumidistat control is set too high

Reduce the desired level of humidity. Combine this with the use of continuous 
exchange mode.

Sudden change in temperature

Wait until outside temperature stabilizes (winter). Heating will also improve 
situation.

Storing too much wood for heating

Store a majority of your wood outside. Even dried, a cord of wood contains 
more than 20 gallons of water.

Dryer vent exhaust is inside home

Make sure the dryer vent is exhausting outside.

Poor air circulation near windows

Open curtains or blinds.

ERV out of balance

Have contractor balance ERV airflows

Well sealed basement door is closed

Open the door or install a grill on the door.

Persistent condensation
on window

Improper adjustment of dehumidistat control

Reduce the desired level of humidity. Combine this step with use of continuous 
exchange mode.

ERV out of balance

Have contractor balance ERV

Poor air circulation near windows

Open curtains or blinds.

Poor Air Flows

1/4" (6mm) mesh on the outside hoods is plugged

Clean exterior hoods or vents

Filters plugged

Remove and clean filter

Core obstructed

Remove and clean core

Indoor grilles closed or blocked

Check and open grilles

Inadequate power supply at site

Have electrician check supply voltage

Ductwork is restricting airflow

Check duct installation

Improper speed control setting

Increase the speed of the ERV (i.e. change unit control from REDUCED to NORMAL 

speed)

ERV airflow improperly balanced

Have contractor balance ERV airflows

Ducting has fallen down or been disconnected from ERV

Have contractor reconnect ducting

Supply air feels cold

Poor location of supply grilles, the airflow may irritate 

the occupant

Locate the grilles high on the walls or under the baseboards, install ceiling
mounted diffuser or grilles so as not to directly spill the supply air on the 
occupant (eg. Over a sofa) 
Turn down the ERV supply speed. A small duct heater (1kw) could be used to 
temper the supply air
Placement of furniture or closed doors is restricting the movement of air in 
the home

Outdoor temperature extremely cold

If supply air is ducted into furnace return, the furnace fan may need to run 
continuously to distribute ventilation air comfortably

ERV and/or Ducts frosting up

ERV air flows are improperly balanced

Have HVAC contractor balance the ERV airflows

Malfunction of the ERV defrost system

Note: minimal frost build-up is expected on the core before unit initiates 

defrost cycle functions

Condensation or Ice Build Up in 
Insulated Duct to the Outside

Incomplete vapor barrier around insulated duct

Tape and seal all joints

A hole or tear in outer duct covering

Tape any holes or tears made in the outer duct covering 
Ensure that the vapor barrier is completely sealed.

Note:

 It is best to get the unit checked by a certified HVAC Contractor/Technician.

Summary of Contents for 463278

Page 1: ...Lenexa KS 66215 Tel 800 747 1762 Fax 800 487 9915 Canada 50 Kanalflakt Way Bouctouche NB E4S 3M5 Tel 800 565 3548 Fax 877 747 8116 VER200 Energy Recovery Ventilator Your ventilation system should be...

Page 2: ...on equipment i e Gas Furnaces Oil Furnaces Wood Stoves etc Products are designed and manufactured to provide reliable performance but they are not guaranteed to be 100 free of defects Even reliable pr...

Page 3: ...Installing the ducting to the weatherhood 9 INTERIOR DUCTING INSTALLATION General Tips 10 Installing duct to ERV 10 Supply Exhaust Air Grilles Location 10 ERV INSTALLATION 11 AIRFLOW ADJUSTMENT BALAN...

Page 4: ...21 53 25 60 28 501 1000 47 93 45 21 53 24 60 28 68 31 75 35 1001 1500 94 139 60 28 68 31 75 35 83 38 90 42 1501 2000 140 186 75 35 83 38 90 42 98 45 105 49 2001 2500 187 232 90 42 98 45 105 49 113 52...

Page 5: ...y areas of the home requiring local exhaust bathroom kitchen laundry room 2 Fresh air is distributed directly to habitable rooms in the house bedrooms living room 3 The ERV s airflow must be balanced...

Page 6: ...g any installation type requiring the use of the furnace interlock Fantech energy recovery ventilators ERV that use a supply fan shutdown for frost prevention do not include an outdoor air motorized d...

Page 7: ...an outdoor air motorized damper If you are using a simplified installation i e connecting the ERV supply air duct to a furnace s return air duct the ERV must operate continuously When the ERV is turne...

Page 8: ...urn ERV Furnace ducting for Simplified Installation Option 2 Suggested installation for When bathroom and kitchen already have local exhaust system May be suitable for retrofitting Benefits Least expe...

Page 9: ...liner which acts as a vapor barrier must be completely sealed to the outer wall and the ERV using tape and or caulking A good bead of high quality caulking preferably acoustical sealant will seal the...

Page 10: ...exible duct to prevent leakage between the ducting and the duct connection In the case of solid ducting slide duct over duct connection screw in place and seal SUPPLY AIR GRILLES LOCATION In homes wit...

Page 11: ...etop fan Central vacuum system Bathroom exhaust fans unless they are specifically designed for this purpose These appliances may cause lint dust or grease to collect in the ERV damaging the unit Mount...

Page 12: ...ke sure to place gasket between the unit and the drain nipple inside the unit 3 Secure the drain nipple using the nutsert 4 Install the drain hose making a P trap secure the condensate line drain conn...

Page 13: ...is operating at normal speed during the balancing sequence When reading with a mechanical type manometer Magnehelic make sure the manometer is placed on a level surface For optimal performance ERV uni...

Page 14: ...rflow may affect the other airflow as well It is recommended to check each airflow again to make sure the value did not change dramatically during the balancing procedure Make adjustments as necessary...

Page 15: ...een LCD ECO mode selects the best operating mode and speed for the season minimizing energy use associated with ventilation Set preferred indoor relative humidity range and ventilation mode for day an...

Page 16: ...e system Use in bathroom kitchen laundry room WALL CONTROLS CONT D MDEH SERIES FEATURES CONNECT TO MDEH1 Rotary dial Dehumidistat Multiple units can be used We recommend setting the relative humidity...

Page 17: ...17 fantech WIRING DIAGRAM Observe polarity on all accessory controls where applicable...

Page 18: ...ONNECTION TO A COOLING SYSTEM On some newer furnaces and older thermostats energizing the R and G terminal at the furnace has the effect of energizing the Y at the thermostat and thereby turning on th...

Page 19: ...Inadequate power supply at site Have electrician check supply voltage Ductwork is restricting airflow Check duct installation Improper speed control setting Increase the speed of the ERV i e change u...

Page 20: ...damages incurred in the use of the ventilation system Fantech is not responsible for providing an authorized service centre near the purchaser or in the general area Fantech reserves the right to sup...

Page 21: ...r core s air inlets facing down place it in a large sink bathtub or shower 4 Pour clean tap water through the face of the core facing upwards until it runs clear Ensure the entire surface is rinsed 5...

Page 22: ...itch 410867 6 Collar 6 Oval w Hole 413893 7 Collar 6 Oval w o Hole 413894 9 Kit RV CTRL Replacement H F 428252 10 Kit Drain Plug 40315 11 Auto Transformer 411963 12 Control Switch 410213 13 Screw Set...

Page 23: ...23 fantech Notes...

Page 24: ...make technical changes For updated documentation please refer to www fantech net Fantech Fantech se r serve le droit de faire des changements tech niques Pour de la documentation jour s il vous pla t...

Reviews: