1. Product Description
DIP Switch Functions
10
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
DIP Switch Functions
The table below describes the DIP switch functions. For a more detailed explaination see "Setting Mode
of Operation" on page 28.
Options
Three optional modules are available for use on the control panel. The control panel provides mounting
slots for two of these optional module boards.
Transmitter Module - 4XTM
The Transmitter Module provides a supervised output for a Local Energy
Municipal Box transmitter and alarm and trouble reverse polarity circuits for
Remote Station Service. Also included is a DISABLE switch and disable
trouble LED.
Note:
As a jumper option, the alarm reverse polarity circuit will open on trouble if no
alarm exists.
Specifications for Local Energy Municipal Box service
(NFPA 72 Auxiliary
Fire Alarm System)
Supervisory current: 5.0 mA.
Trip current: 0.35 amps (subtracted from Notification Appliance
power).
Coil Voltage: 3.65 VDC.
Coil resistance: 14.6 ohms.
Maximum allowable wire resistance between panel and trip coil: 3 ohms.
Municipal Box wiring can leave the building.
Specifications for Remote Station Service
(NFPA 72 Remote Station Fire Alarm System)
Maximum load for each circuit: 10 mA.
Reverse polarity output voltage: 24 VDC.
Remote Alarm and Remote Trouble wiring can leave the building.
Zone Relay Module - 4XZM
The Zone Relay module provides Form-C contacts for the following:
• Relay #1 - Alarm Detected / First Alarm
• Relay #2 - Alarm Detected / Second Alarm
• Relay #3 - Release 1 / Release 1
• Relay #4 - Release 2 / Not Used
• Relay #5 - General Alarm
• Relay #6 - System Trouble
Note:
As a jumper option, the first four relays can be made silenceable.
Specifications
Dry Form-C contacts rated: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30
VAC (resistive).
#1
Cross Zone
Determines how NACs and Releasing Circuits respond to an alarm.
#2
Supervisory
Selects Releasing Circuit #2 to function as a Supervisory Circuit.
#3 & #4
Timer
Selects Timer Delay setting.
#5 & #6
Abort
Selects a variety of abort functions.
Note:
See “Setting Mode of Operation” on page 28 for a more detailed explanation of DIP switch
functions.
T B 1
T B L
J 1
J 2
4X
T
M
F
.cdr
T B 1
L AT C H
D IS A B L E
J 2
4
X
Z
M
F
.cdr
Summary of Contents for PDRP-1002 Series
Page 32: ...2 Installation Power Up Procedure 32 PDRP 1002 Instruction Manual PN 51135 B0 04 06 01 Notes...
Page 38: ...3 System Operation System Events 38 PDRP 1002 Instruction Manual PN 51135 B0 04 06 01 Notes...
Page 58: ...58 PDRP 1002 Instruction Manual PN 51135 B0 04 06 01...
Page 59: ...PDRP 1002 Instruction Manual PN 51135 B0 04 06 01 59...