Setting Mode of Operation
2. Installation
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
29
Switch #2 - Supervisory/Releasing Service
Set the function of Releasing Circuit #2 by setting this switch.
Switch #3 and #4 - Timer Delay
Select the desired timer setting and set these switches accordingly.
Switch # 5 and #6 - Abort Function
Select the desired Abort Functions for delaying the activation of releasing circuits, and set these switches
accordingly. If ‘Cross Zone’ is selected, both IDC #1 and IDC #2 must be activated to start timer.
OFF
ON
REL #2
Will function as a solenoid releasing
circuit.
Note:
This circuit is nonpower-
limited.
REL #2
Will function as a supervisory input
circuit.
• A short condition on this circuit
will light the Supervisory LED
and sound the supervisory tone on
the control panel piezo.
• An open condition generates a
circuit trouble condition.
Note:
This circuit will now be power-
limited.
No Delay*
10 Second
20 Second
30 Second
Switch #3
OFF
OFF
ON
ON
Switch #4
OFF
ON
OFF
ON
* Abort timer will not operate when timer is set for ‘No Delay’.
Switch #5
OFF
OFF
ON
ON
Switch #6
OFF
ON
OFF
ON
Standard UL-type
delay timer
IRI-type delay
timer
NYC-type delay
timer
Local Jurisdiction
delay timer
Continues to count
down upon ABORT, but
stops and holds at 10
seconds until release of
the ABORT switch.
Upon release of the
ABORT switch, the
timer resumes the
countdown at 10
seconds.
Functions the same as
the UL-type timer with
the exception that the
ABORT will function
only if pressed and held
before 2nd zone goes
into alarm.
When an alarm exists,
pressing ABORT
changes timer value to
the Timer Delay plus 90
seconds. The timer will
not start while ABORT
is held. SYSTEM
RESET restores timer to
origional Timer Delay.
Each time ABORT is
pressed again adds 90
seconds to Timer Deley.
Once the timer has
started, pressing
ABORT resets the timer
to full Timer Delay. The
timer will not start
while ABORT is held.
Releasing the ABORT
switch continues the
countdown; pressing
ABORT again restores
Timer Delay to its full
value.
Note:
Abort timer will not operate when timer is set for ‘No Delay’. Manual pull station does not use
abort mode.
These modes are the only ones that
comply with UL Standard 864.
Summary of Contents for PDRP-1002 Series
Page 32: ...2 Installation Power Up Procedure 32 PDRP 1002 Instruction Manual PN 51135 B0 04 06 01 Notes...
Page 38: ...3 System Operation System Events 38 PDRP 1002 Instruction Manual PN 51135 B0 04 06 01 Notes...
Page 58: ...58 PDRP 1002 Instruction Manual PN 51135 B0 04 06 01...
Page 59: ...PDRP 1002 Instruction Manual PN 51135 B0 04 06 01 59...